20
Go to Section 2.2 for detailed explanation of the programming parameters on this page.
Table 3.3 - Programming Performa Cv 962 TC Electronic Time Clock Filter
Parameter
Description
Range of
Values
Minimum
Increment
Recommended
Program
Value
Units of
Measure
Notes
P1
Day of week and
time of day
(1-7)
1:00-12:59
AM or PM
Metric
(1-7)
0:00-23:59
(1 day)
1 Minute
Current Day and
Time
Hour
Minute
Range depends on value selected for P13.
For day of week SUN=1, MON=2, TUE=3,
WED=4, THU=5, FRI=6, SAT=7,. THIS IS
THE LEFT MOST DIGIT ON THE DISPLAY
P2
Time of day to start
backwash
1:00-12:59 AM
or PM
00:00-23:59
As required
Hour
Minute
Range depends on value selected for P13
P3
Program as
recommended
10
100
U.S.
Metric
P4
Program as
recommended
0.5
P5
Program as
recommended
As required
U.S.
Metric
P6
Program as
recommended
2-200
1
200
P7
Program as
recommended
2-200
1
200
P9
Backwash time
7-60
1
14*
Minutes
*May be adjusted for application.
P10
Program as
recommended
7
Minutes
P11
Fast Rinse time
9-60
1
9*
Minutes
*May be adjusted for application.
P12
Units of measure
0-1
1
0
0 = US, 1 = Metric
P13
Clock mode
0-1
1
0
0 = 12 hour clock, 1 = 24 hour clock
P14
Interval
Regeneration
0-30
1
0
Days
0 = no interval selected. *May be adjusted for
application.
P15
Does not apply for
Time Clock operation
P16
Does not apply for
Time Clock operation
P17
Operation type
0-7
1
7
7 = Single 962FTC
P18
Salt/Capacity
Change Lock out
0-1
1
0
0 = none, 1 = Salt/Capacity change locked out
P19
Does not apply for
Time Clock operation
P20
Does not apply for
Time Clock operation
P21
Remote
Regeneration Switch
Delay
0-254
1
60
Seconds
Time remote switch must be active to start a
backwash
P22
Factory Use Only -
DO NOT CHANGE
99
Reynolds Water Conditioning Co.
24545Hathaway
Farmington Hills, MI 48335
800-572-9575