17
Go to Section 3.2 for detailed explanation of the programming parameters on this page.
Table 2.5 - Programming Performa Cv 962TC Electronic Time Clock Softener
Parameter
Description
Range of
Values
Minimum
Increment
Recommended
Program
Value
Units of
Measure
Notes
P1
Day of Week and
Time of Day
(1-7)
1:00-12:59
AM or PM
Metric
(1-7)
0:00-23:59
(1 day)
1 Minute
Current Day and
Time
Hour
Minute
Range depends on value selected
for P13. For day of week SUN=1,
MON=2, TUE=3, WED=4, THU=5,
FRI=6, SAT=7,. THIS IS THE LEFT
MOST DIGIT ON THE DISPLAY
P2
Time of day to start
regeneration
1:00-12:59 AM
or PM
00:00-23:59
As required
Hour
Minute
Range depends on value selected
for P13
P3
As recommended
10
P4
Salt amount
.5-125.0
.2-50.0
.5
.2
Selected from Table
2.2
Pounds
Kilograms
P5
Program as
Recommended
10
P6
Refill controller
2-200
1
Selected from Table
2.2
This number tells the controller the
rate of refill based on the refill
control installed. Refill dwell time is
calculated to refill the proper
amount of water into brine tank.
P7
Brine draw rate
2-200
1
Selected from Table
2.2
This number tells the controller the
draw rate based on the injector
size. The swell time in the draw
position is then calculated.
P9
Backwash time
4-60
1
14*
Minutes
*May be adjusted for application
P10
Slow Rinse time
7-125
1
40*
Minutes
*May be adjusted for application.
This time does not include the
calculated brine draw time.
P11
Fast Rinse time
2-60
1
4*
Minutes
*May be adjusted for application
P12
Units of measure
0-1
1
0
0 = US, 1 = Metric
P13
Clock mode
0-1
1
0
0 = 12 hour clock, 1 = 24 hour clock
P14
Interval Regeneration
Calendar override
0-30
1
0
Days between
regeneration
0 = no interval chosen - *May be
adjusted for application.
P15
Does not apply for
Timeclock operation
0
P16
Does not apply for
Timeclock operation
30
P17
Operation type
3-4
1
6
6 = Single 962TC
P18
Salt Change Lock out
0-1
1
0
0 = none, 1 = Salt/Capacity change
locked out
P19
Does not apply for
Timeclock operation
P20
Does not apply for
Timeclock operation
P21
Remote
Regeneration Switch
Delay
0-254
1
60
Seconds
Time remote switch must be active
to start a regeneration
P22
Factory Use Only -
DO NOT CHANGE
99