H8: I/O card parameters
Code
Name
Setting range
Default
Min.
Attri.
H8.00
EX1 input
0...41
0
–
Stop
H8.01
EX2 input
0
–
Stop
H8.02
EX3 input
0
–
Stop
H8.03
EX4 input
0
–
Stop
H8.05
EAI input mode
0: 0...20 mA
1: 4...20 mA
2: 0…10 V
3: 0…5 V
4: 2...10 V
5: -10...10 V
0
–
Stop
H8.06
EAI input polarity setting
0...2
1
–
Stop
H8.08
EAI curve selection
0: Curve 0
1: Curve 1
2: Curve 2
1
–
Stop
H8.09
EAI filter time
0.000...2.000
0.100
0.001
Run
H8.10
EAI gain
0.00...10.00
1.00
0.01
Run
H8.15
Input curve 0 minimum
-120.0 %...[H8.17]
0.0
0.1
Run
H8.16
Input curve 0 minimum frequency
-[E0.09]...[E0.09] Hz
0.00
0.01
Run
H8.17
Input curve 0 maximum
[H8.15]...120.0 %
100.0
0.1
Run
H8.18
Input curve 0 maximum frequency
-[E0.09]...[E0.09] Hz
50.00
0.01
Run
H8.20
EDO output setting
0...20
1
–
Stop
H8.21
Extended relay output selection
1
–
Stop
H8.25
EAO output mode
0: 0…10 V
1: 0...20 mA
0
–
Run
H8.26
EAO output selection
0: Running frequency
1: Set frequency
2: Output current
4: Output voltage
5: Output power
6: AI1 analog input
7: AI2 analog input
8: EAI analog input
11: Motor temperature sensor pow‐
er
0
–
Run
Bosch Rexroth AG
DOK-SYTROX-FCP5020****-IT01-EN-P
166/201
Frequency-controlled pump drive system Sytronix FcP 5020
Commissioning of Sytronix FcP 5020 System