7.11.4
Group E: Function Control Parameters
E0: Set point and control parameters
Code
Name
Setting range
Default
Min.
Attri.
E0.00
First frequency setting source
0...99
0
–
Stop
E0.01
First run command source
0...2
0
–
Stop
E0.02
Second frequency setting source
0...99
2
–
Stop
E0.03
Second run command source
0...2
1
–
Stop
E0.04
Frequency setting source
combination
0...2
0
–
Stop
E0.06
Digital setting frequency
saving mode
0...3
0
–
Stop
E0.07
Digital setting frequency
0.00...[E0.09] Hz
50.00
0.01
Run
E0.08
Maximum output frequency
50.00...400.00 Hz
50.00
0.01
Stop
E0.09
Output frequency high limit
[E0.10]...[E0.08] Hz
50.00
0.01
Run
E0.10
Output frequency low limit
0.00...[E0.09] Hz
0.00
0.01
Run
E0.11
Reverse running frequency
0.00...[E0.09] Hz
0.00
0.01
Run
E0.15
Low speed running setting
0: Run with 0.00 Hz
1: Run with low limit
frequency
0
–
Stop
E0.16
Low speed frequency hysteresis
0.00...[E0.10] Hz
0.00
0.01
Stop
E0.17
Direction control
0: Forward / Reverse
1: Forward only
2: Reverse only
3: Swap default direction
0
–
Stop
E0.18
Direction change dead time
0.0...60.0 s
1.0
0.1
Stop
E0.25
Acceleration / deceleration
curve mode
0: Linear mode
1: S-curve
0
–
Stop
E0.26
Acceleration time
0.1...6,000.0 s
DOM
0.1
Run
E0.27
Deceleration time
0.1...6,000.0 s
DOM
0.1
Run
E0.28
S-curve starting phase factor
0.0...40.0 %
20.0
0.1
Stop
E0.29
S-curve stopping phase factor
0.0...40.0 %
20.0
0.1
Stop
E0.35
Start mode
0: Start directly
1: DC-braking before start
2: Start with speed capture
3: Automatic start / stop according
to setting frequency
0
–
Stop
E0.36
Start frequency
0.00...50.00 Hz
0.05
0.01
Stop
E0.37
Start frequency holding time
0.0...20.0 s
0.0
0.1
Stop
Bosch Rexroth AG
DOK-SYTROX-FCP5020****-IT01-EN-P
150/201
Frequency-controlled pump drive system Sytronix FcP 5020
Commissioning of Sytronix FcP 5020 System