E263 Velocity command value > limit S-0-0091
Cause:
S-0-0036, Velocity Command Value
is outside the allowed range of
values.
Remedy:
It is limited to
S-0-0091, Bipolar velocity limit value
.
See also the functional description: "Operating Mode: Velocity Control"
E324 Option module error power supply unit
Cause:
A component that is connected to the HVE or HVR power supply unit
reports a malfunction.
Remedy:
Check the option module, and replace it if necessary.
E325 Recovery overload power supply unit
Cause:
The regenerated load of the drives is excessive.
Remedy:
Reduce allowable deceleration. Use a drive controller with a smaller peak
currents.
E326 Bus power overload
Error will be stored for no more than 500 ms!
Cause:
The input power required by the drives is excessive.
Remedy:
Reduce the allowable acceleration. Use a drive controller a with smaller
peak current.
E350 Heat sink overtemp. warning power supply unit
The permissible heatsink temperature has been reached. The
temperature pre-warning contact is open. Power will be switched off after
30 s.
Cause:
1.
Load too high
2.
Ambient temperature too high
3.
Cooling air is blocked
4.
Blower in unit is defective
Summary of Contents for DIAX04
Page 4: ...About this Documentation DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Page 14: ...1 4 Diagnostic Message Descriptions DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Page 106: ...6 2 Index DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P W Warning symbols 3 1...
Page 113: ......
Page 114: ...Printed in Germany 2 9 1 6 2 8...