11-12
s
r
e
ll
o
r
t
n
o
C
e
v
i
r
D
3
0
E
V
I
R
D
O
C
E
s
n
o
it
c
e
n
n
o
C
s
n
i
a
M
Q1 Fuse and K1 Contactor
When selecting a mains contactor and fuses, the continuous current in
the supply leads as well as the starting inrush current must be taken into
account. Several controllers can be operated on a single fuse and mains
contactor. The phase currents and inrush currents of the individual drives
must then simply be added up. If a transformer is used, then the fuses
and contactors must be installed on the primary side.
The Siemens type fuses and contactors in the selection table below are
only examples. Products of equal rating from other manufacturers can be
used.
Phase
current
Lead cross
sections
(1)
Fuses
(triggering
characte.
C)
(2)
Power fuses
(3)
Fusible
links
(operating
class
gl)
(2)
Mains
contactor
(3)
Inrush
current
Dropout delay
t
Abmax
Pull-up delay
t
Anmax
in A
mm
2
Current
in A
Siemens type
Current in A Siemens
type
in A
in ms
in ms
9
1.0
10
3VU1300- .ML00
or
3RV1011-1JA10
10
3TF40
or
3RT1016
54
80
120
12
1.5
16
3VU1300- .MM00
or
3RV1021-4AA10
16
3TF41
or
3RT1017
72
80
120
16
2.5
20
3VU1300- .MM00
or
3RV1021-4AA10
20
3TF42
or
3RT1025
96
110
190
22
4.0
25
3VU1300- .MP00
or
3RV1021-4DA10
25
3TF43
or
3RT1026
132
110
190
32
6.0
32
3VU1600- .MP00
or
3RV1031-4EA10
35
3TF44
or
3RT1034
186
200
120
1. Lead cross sections per EN 60204
– Installation B1 – correction factors not taken into account.
2. With recommended fuses short-term operating loads can be used by the drive for two minutes. If this is needed for
extended periods, then use a bigger fuse.
3. Allocation "2" per DIN IEC 60947-4: easily separable contact welding at contactors are permitted as a result of
short circuits.
Fig. 11-13: Selecting table for Q1 fuses and K1 contactors
Note:
To make sure the mains contactor is not overloaded by the
load current in the case of frequent switching off, you first have
to switch off the drive via the drive enable in the master
communication and then switch off the mains contactor.
|