RX62T YROTATE-IT-RX62T Motor Control Kit
UM-YROTATE-IT-RX62T Rev.1.00
Page 41 of 51
Jan 15, 2014
k) Set a start-up current equal to 25% of the maximum current. In our case 25% of 3.5A is 0.875A. Please enter the
value 875 into the parameter n°6 and click on the “write” button on the left.
Let’s close the window.
l) Please click on the button: “Speed Control”:
To start the motor, let’s enter a speed which is 1.5 times the minimum speed, in this case
1500 RPM