2.3 Performance data
Cooling capacity RVT 265 DC
Inside
Outside temperature (TK, °C)
20
25
30
Cooling capacity (A = Total, B = Sensitive, C = Power consumption)
TK
FK
A
B
C
A
B
C
A
B
C
°C
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
20
14
2.71
2.11
0.37
2.59
2.07
0.40
2.48
2.03
0.43
22
16
2.85
2.18
0.37
2.73
2.14
0.40
2.61
2.10
0.44
25
18
3.00
2.25
0.37
2.87
2.21
0.41
2.74
2.17
0.44
27
19
3.06
2.27
0.38
2.93
2.23
0.41
2.80
2.18
0.44
30
22
3.28
2.38
0.38
3.14
2.34
0.41
2.99
2.29
0.45
32
24
3.40
2.43
0.38
3.25
2.39
0.42
3.11
2.35
0.45
Inside
Outside temperature (TK, °C)
35
40
Cooling capacity (A = Total, B = Sensitive, C = Power consumption)
TK
FK
A
B
C
A
B
C
°C
°C
kW
kW
kW
kW
kW
kW
20
14
2.33
1.96
0.47
2.29
1.97
0.50
22
16
2.46
2.03
0.48
2.41
2.04
0.51
25
18
2.59
2.10
0.48
2.54
2.10
0.51
27
19
2.64
2.11
0.48
2.59
2.12
0.52
30
22
2.82
2.22
0.49
2.77
2.23
0.52
32
24
2.93
2.27
0.49
2.87
2.28
0.52
REMKO RVT series