Cooling capacity RVT 355 DC
Inside
Outside temperature (TK, °C)
20
25
30
Cooling capacity (A = Total, B = Sensitive, C = Power consumption)
TK
FK
A
B
C
A
B
C
A
B
C
°C
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
20
14
3.55
2.77
0.57
3.41
2.72
0.62
3.26
2.67
0.67
22
16
3.73
2.86
0.58
3.59
2.81
0.63
3.43
2.76
0.68
25
18
3.93
2.95
0.58
3.77
2.91
0.63
3.61
2.85
0.69
27
19
4.01
2.97
0.59
3.85
2.93
0.64
3.68
2.87
0.69
30
22
4.29
3.11
0.59
4.12
3.07
0.64
3.94
3.01
0.70
32
24
4.45
3.18
0.59
4.27
3.14
0.65
4.09
3.08
0.70
Inside
Outside temperature (TK, °C)
35
40
Cooling capacity (A = Total, B = Sensitive, C = Power consumption)
TK
FK
A
B
C
A
B
C
°C
°C
kW
kW
kW
kW
kW
kW
20
14
3.11
2.61
0.73
3.02
2.59
0.78
22
16
3.27
2.70
0.74
3.18
2.68
0.79
25
18
3.45
2.79
0.75
3.34
2.77
0.80
27
19
3.52
2.81
0.75
3.41
2.80
0.80
30
22
3.76
2.96
0.76
3.65
2.94
0.81
32
24
3.90
3.03
0.76
3.79
3.01
0.81
REMKO RVT series