10.1.4 Locking
Tab.47 Locking codes
Code
Display text
Description
Solution
E.00.00
TFlow Open
Flow temperature sensor is either
removed or measures a temperature
below range
Zone flow temperature sensor open:
Sensor is not present.
Wrong Zone Function setting: check the setting
of parameter CP02x.
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: make sure that the
sensor has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.01
TFlow Closed
Flow temperature sensor is either
shorted or measures a temperature
above range
Zone flow temperature sensor short-circuited:
Sensor is not present.
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.04
TReturn Open
Return temperature sensor is either
removed or measures a temperature
below range
Return temperature sensor open:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.00.05
TReturn Closed
Return temperature sensor is either
shorted or measures a temperature
above range
Return temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.00.08
THeat Ex Open
Heat exchanger temperature sensor
is either removed or measures a
temperature below range
Heat exchanger temperature sensor open:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.09
THeat Ex Closed
Heat exchanger temperature sensor
is either shorted or measures a tem
perature above range
Heat exchanger temperature sensor short-circuit
ed:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.20
TFlue Gas Open
Flue gas temperature sensor is ei
ther removed or measures a temper
ature below range
Open circuit in flue gas sensor:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.21
TFlue Gas Closed
Flue gas temperature sensor is ei
ther shorted or measures a tempera
ture above range
Flue gas sensor short-circuited:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
10 Troubleshooting
52