L Length of the flue gas outlet channel to roof feed-through
Connecting the flue gas outlet
Connecting the air supply
With a room-ventilated version, the air supply opening stays open; only the
flue gas outlet opening is connected. This will ensure that the boiler
obtains the necessary combustion air directly from the installation area.
Use adapters when using air supply and flue gas outlet pipes with
diameters other than 150 mm.
Caution
The air supply opening must stay open.
The installation area must be equipped with the necessary air
supply openings. These openings must not be obstructed or
shut off.
If the boiler is operated in a dusty environment (e.g. during the
construction phase), use of an air inlet filter is necessary.
Tab.11 Maximum chimney length (L)
90 mm
100 mm 110 mm 130 mm 150 mm
Quinta Ace 135
8 m
12 m
23 m
40 m
Quinta Ace 160
5 m
8 m
15 m
37 m
(1) With retention of the maximum flue length it is possible to apply an extra 5
times 90º or 10 times 45º elbows.
Room-sealed model (C
13
, C
33
)
L Length of the concentric flue gas outlet channel to roof feed-
through
Connecting the flue gas outlet
Connecting the air supply
With a room-sealed version, both the flue gas outlet and the air supply
openings are connected (concentrically). Use adapters when using air
supply and flue gas outlet pipes with diameters other than 100/150 mm.
Tab.12 Maximum chimney length (L)
100/150 mm
130/200 mm
150/220 mm
Quinta Ace 135
5 m
20 m
Quinta Ace 160
1 m
12 m
(1) Retaining the maximum chimney length, it is possible to use an extra 5 x
90º or 10 x 45º elbows.
Fig.9
Room-ventilated version
AD-0000220-01
L =
Fig.10
Room-sealed version
AD-0000219-01
L =
4 Preparation of installation
18
7701838 - v.09 - 10122021