Connection in different pressure areas (C
53
)
L Total length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
Combustion air supply and flue gas discharge are possible in different
pressure areas and semi-CLV systems, with the exception of the coastal
area. The maximum permitted height difference between the combustion
air supply and the flue gas outlet is 36 m.
Tab.13 Maximum chimney length (L)
90 mm
100 mm 110 mm 130 mm 150 mm
Quinta Ace 135
-
6 m
15 m
40 m
Quinta Ace 160
-
-
9 m
27 m
(1) With retention of the maximum flue length it is possible to apply an extra 5
times 90º or 10 times 45º elbows.
Reduction table
Tab.14 Pipe reduction for each bend - radius ½D (parallel)
Diameter
100 mm 110 mm 130 mm 150 mm
45° bend
1.4 m
1.5 m
1.6 m
-
90° bend
4.9 m
5.4 m
6.2 m
-
Tab.15 Pipe reduction for each bend - radius ½D (concentric)
Diameter
100/150 mm
130/200 mm
150/220 mm
45° bend
1.0 m
1.5 m
1.5 m
90° bend
2.0 m
3.0 m
3.0 m
Tab.16 Pipe reduction for each bend - radius 1D (parallel)
Diameter
100 mm 110 mm 130 mm 150 mm
45° bend
-
-
1 m
1.2 m
90° bend
-
-
1.8 m
2.1 m
4.5.5
Additional guidelines
Installation
For installing the flue gas outlet and air supply materials, refer to the
instructions of the manufacturer of the relevant material. After
installation, check at least all flue gas outlet and air supply parts for
tightness.
Warning
If the flue gas outlet and air supply materials are not installed in
accordance with the instructions (e.g. not leak-proof, not correctly
bracketed), this can result in dangerous situations and/or physical
injury.
Make sure that the flue gas outlet pipe towards the boiler has a sufficient
gradient (at least 50 mm per metre) and that there is a sufficient
condensate collector and discharge (at least 1 m before the outlet of the
boiler). The bends used must be larger than 90° to guarantee the
gradient and a good seal on the lip rings.
Fig.11
Different pressure zones
AD-0000114-01
L =
+
Fig.12
Bend radius ½D
AD-3001608-01
R=½D
D
Fig.13
Bend radius 1D
AD-3001609-01
D
R=1D
4 Preparation of installation
7701838 - v.09 - 10122021
19