Code
Display text
Description
Adjustment range
Submenu
135
160
AP090
Installer phone
Telephone number of the installer
Mandatory
bus master
6
6
CP040
Postrun zone
pump
Pump post runtime of the zone
0 - 20 Min
CH
0
0
CP240
ZoneRoomUni
tInfl
Adjustment of the influence of the
zone room unit
0 - 10
CH
3
3
CP250
CalSondeAmb
Zone
Calibration of Zone Room Unit
-5 - 5 °C
CH
0
0
CP290
ConfigZone
PumpOut
Configuration of Zone Pump Out
put
0 = Zone output
1 = CH mode
2 = DHW mode
3 = Cooling mode
4 = Error report
5 = Burning
6 = Service flag
7 = System error
8 = DHW looping
CH
0
0
CP510
Temporary
Room Setp
Temporary room setpoint per zone 5 - 50 °C
CH
20
20
GP030
Flue Gas Temp
Max
Maximum flue gas temperature
20 - 200 °C
Commercial
boiler
120
120
GP048
Fan PWM Min
Minimum Pulse Width Modulation
for the fan controller
0 - 100 %
GVC Pneu
matic
10
10
GP050
Power Min
Minimum power in kilo Watt for
RT2012 calculation
0 - 300 kW
Commercial
boiler
5.3
5.3
GP056
Grad. 1 power
reduct
Factor of power reduction when
temperature gradient > parHeDTh
MaxLevel1 is detected
0 - 1000
Commercial
boiler
1
1
PP017
ChPumpSpeed
MaxFactor
Maximum central heating at mini
mum load as percentage of max
pump speed
0 - 100 %
Commercial
boiler
30
30
9 Maintenance
9.1
Maintenance regulations
Important
The boiler must be maintained by a qualified installer in
accordance with local and national regulations.
Important
Adjust the frequency of inspection and service to the conditions of
use. This applies especially if the boiler is:
In constant use (for specific processes).
Used with a low supply temperature.
Used with a high ΔT.
9 Maintenance
7701838 - v.09 - 10122021
45