4 Preparation of installation
4.1
Installation regulations
Important
The Quinta Ace must be installed by a qualified installer in
accordance with local and national regulations.
Warning
The installer must be registered with Gas Safe and have the
correct ACS qualifications.
Important
Practical guidelines - see the latest version.
4.2
Choice of the location
4.2.1
Location of the boiler
Use the guidelines and the required installation space as a basis for
determining the correct place to install the boiler.
When determining the correct installation space, take account of the
permitted position of the flue gas discharge and/or air supply outlet.
Ensure that there is sufficient space around the boiler for good access
and ease of maintenance.
Danger
It is forbidden to store, even temporarily, combustible products
and substances in the boiler or near the boiler.
Caution
Mount the boiler on a strong and solid wall (at least half-brick
brickwork with calcium silicate bricks). Build a reinforcing
structure if necessary.
The boiler must be installed in a frost-free area.
The boiler must have an earthed electrical connection.
A connection to the drain must be present for the condensate
drain close to the boiler.
The specified minimum space is required for standard
maintenance work. For installation and extensive servicing
work, there must be at least 1 m x 1 m of clear space in front of
the boiler.
Caution
If the power cord is permanently connected, you must always
install a main bipolar switch with an opening gap of at least 3 mm
(BS EN 60335-1).
Fig.3
Installation area
AD-0000104-03
600
30
30
m
in
. 10
00
60
0
m
in.
500
mi
n.
30
0
104
5
m
in.
10
00
4 Preparation of installation
12
7701838 - v.09 - 10122021