9.4
Disposal and recycling
Caution
Only qualified professionals are permitted to remove and dispose
of the boiler, in accordance with local and national regulations.
If you need to remove the boiler, proceed as follows:
1. Switch off the boiler.
2. Cut the power supply to the boiler.
3. Close the main gas valve.
4. Close the water mains.
5. Close the gas valve on the boiler.
6. Drain the installation.
7. Remove the air/flue gas pipes.
8. Disconnect all pipes.
9. Dismantle the boiler.
10 Troubleshooting
10.1 Error codes
The Quinta Ace is fitted with an electronic regulation and control unit. The
heart of the control is a e-Smart microprocessor, which controls and also
protects. In the event of an error, a corresponding code is displayed.
Tab.44 Error codes are displayed at three different levels
Code
Type
Description
Warning
The controls continue to operate, but the cause of the warning must be investigated. A
warning can change into a blocking or lock-out.
Blocking
The controls will stop normal operation, and will check with set intervals if the cause of
Normal operation will resume when the cause of the blocking
has been rectified. A blocking can become a lock-out.
Lock out
The controls will stop normal operation. The cause of the lock-out must be rectified and
the controls must be reset manually.
(1) The first letter indicates the type of error.
(2) For some blocking errors, this checking interval is ten minutes. In those cases, it may seem that the controls do not start automatically.
Wait ten minutes before resetting.
The meaning of the code can be found in the various error code tables.
Important
The error code is needed to find the cause of the error quickly and
correctly and for any support from Remeha.
10.1.1 Display of error codes
When an error occurs in the installation, the control panel will show the
following:
1 The display will show a corresponding code and message.
2 The status LED of the control panel will show:
Continuous green = Normal operation
Flashing green = Warning
Continuous red = Blocking
Flashing red = Lock out
When an error occurs, proceed as follows:
1. Press and hold the button to reset the appliance.
The appliance starts up again.
Fig.58
MW-3000179-03
Fig.59
Error code display on HMI T-control
AD-3001379-01
Error Code: A.00.00
..... ... ....... .... .. ..... ....... .... ..... .......
i
........ .......
Home Screen
22/02/2018 11:20
20/02/2018 16:51
.......... ......... .... ............ ........... ... ..... ....
...... ..... ......... ... ....... .......
.......... .........
... .........
1
2
10 Troubleshooting
7701838 - v.09 - 10122021
47