Tab.33 Checking/setting values for O
2
at full load for BREEAM with
G30/G31 (butane/propane)
Values at full load for G30/G31 (butane/propane)
BREEAM
O
2
Quinta Ace 135
6.6 - 6.9
Quinta Ace 160
6.6 - 6.9
(1) Nominal value
(2) These values are only applicable when the fan speeds have been set
for BREEAM.
Caution
The O
2
values at full load must be lower than the O
2
values at low
load.
3. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
4. Use adjusting screw A to set the percentage of O
2
to the nominal
value, for the gas type being used. This must always be between the
highest and lowest setting limit.
Performing the low load test
1. If the full load test is still running, press the button to change the
load test mode.
2. If the full load test was finished, select the tile [ ] to restart the
chimney sweep menu.
A Change load test mode
B Low power
3. Select the Low power test in the menu Change load test mode.
The low load test starts. The selected load test mode is shown in
the menu and the icon appears in the top right of the screen.
4. Check the load test settings and adjust if necessary.
Only the parameters shown in bold can be changed.
5. End the low load test by pressing the button.
The message Running load test(s) stopped! is displayed.
Checking/setting values for O
2
at part load
1. Measure the percentage of O
2
in the flue gases at part load.
2. Compare the measured value with the checking values in the table.
Tab.34 Checking/setting values for O
2
at part load for G20 (H gas)
Values at part load for G20 (H gas)
O
2
Quinta Ace 135
5.2
- 5.6
Quinta Ace 160
5.2
- 5.6
(1) Nominal value
Fig.47
Location of adjusting screw A
AD-0000139-02
2
1
A
Fig.48
Low load test
AD-3000941-03
..... ... ....... .... .. ..... ....
.........
..... ... ....... ....
..... ... ....... ....
....... .... .. ..... ....
.......
....... ...........
......
.....
...
.....
..... ... ....... .... .. ..... ....... .... ..... .......
i
.....
....... .... ....... .... .......
.... ...... ....
... ......
11:20
A
B
7 Commissioning
38
7701838 - v.09 - 10122021