8 - PARAMETER QUICK REFERENCE GUIDE
49'1329 e
GV3000/SE
8 - 5
GV3000/SE Regulator, V/Hz Mode Parameters (H.xxx)
* =
Parameter tune
a
ble at drive stopped or running; all others adjust with drive stopped.
N/A
= not available
Para-
meter
Description
V/Hz control mode only
Selection / Adjustment Range
EUr-Init.
Setting
Actual
Setting
H.000
(1)
Motor Nameplate Volts
180 - 690 VAC
380VAC
H.001
Mot. Namepl. Base Frequency
30.0 -200.0 Hz (frequency at nominal voltage)
50.0 Hz
H.002
Motor Nameplate Amps
Power module-dependent
P/U dep.
H.003
Torque Boost Voltage
0.0 - 20.0% of nominal motor voltage
0.5%
*H.004
Slip Compensation
0.0 - 10.0% of base frequency (H.001) added to freq. ref.
0.0%
*H.005
D-C Braking Enable
OFF - Disable DC Braking
ON - Enable DC Braking
OFF
*H.006
D-C Braking Start Frequency
0.5 Hz - Value in P.004 (Maximum Hz) in Hz
1.0 Hz
*H.007
D-C Braking Current
0.0% - 100.0% of Motor Nameplate Amps
10%
*H.008
D-C Braking Time
0.0 - 10.0 s
3.0 s
*H.009
Avoidance Frequency Enable
OFF - Disable avoidance freq., 'ON' - Enable avoid. freq.
OFF
*H.010
Avoidance Freq. 1, Midpoint
0.0 - 200.0 Hz
0.0 Hz
*H.011
Avoidance Frequency 1, Band
2.0 - 10.0 Hz
2.0 Hz
*H.012
Avoidance Freq. 2, Midpoint
0.0 - 200.0 Hz
0.0 Hz
*H.013
Avoidance Frequency 2, Band
2.0 - 10.0 Hz
2.0 Hz
*H.014
Avoidance Freq. 3, Midpoint
0.0 - 200.0 Hz
0.0 Hz
*H.015
Avoidance Frequency 3, Band
2.0 - 10.0 Hz
2.0 Hz
H.016
(4)
Sync. Direction
(Start into rotating motor)
(
GV3000/SE
searches
motor RPM starting at max.
frequency and synchronizes its
reference)
OFF - Disable Synchronisation (fx = max.freq.)
F - Searching starts at +fx (forward)
r - Searching starts at
-
fx (reverse)
Fr - Searching starts at
+
fx, then at
-
fx
rF - Searching starts at
-
fx, then at +fx
OFF
H.017
Input Power/ Snubber
Configuration
0= AC input with bus-regulator, with ride-thru enabled
1= AC input w/o bus-regul., with ride-thru a. Dyn. Braking
2= DC input with bus-regul., w/o ride-thru (System 1-Q)
3= DC input w/o bus-regul., w/o ride-thru (System 4-Q)
4= DC input with bus-regul., with ride-thru (Single drive)
5= DC input w/o bus-regul., with ride-thru and Dyn. Brak.
0
H.018
V/Hz Curve Type
0 - Linear V/Hz curve
1 - Optimized curve for 'RPM AC' motors
2 - Squared V/Hz curve
0
H.019
(6)
Identification Result
(Output Variable only)
0 = Ident. Procedure successful
1 = Logged error aborted Ident. Procedure
2 = Function Loss aborted Ident. Procedure
3 = STOP command aborted Ident. Procedure
4 = Current feedback too low. Ident. aborted.
6 = Result out of range. Ident. aborted.
N/A
H.020
(1)(6)
Identification Request
OFF - Disable Identification Procedure
ON - Enable Identification Procedure
OFF
H.021
(10)
A-C Line Voltage
300- 565 VAC
(enter value /-10% of actual line voltage)
380 VAC
H.022
Overfrequency Limit
30.0 - 4 x H.001 +5% or 210 Hz
(on type V/Hz)
90 Hz
Notes: (1) P.047, P.005 and H.000 must be set before activating at V/Hz mode the Identification Request (H.020)
(4) Don’t set H.016 (Sync. Mode Select) to any value but ‘F’ avoiding REVERSE rotation via P.027 (Reverse Disable)
(6) See Section 5 for Identification Request Result Procedure.
(10) See Section 2, Table 2-5, Note 1) of power units manual 49'1327, if the internal Braking Unit option is provided.
Summary of Contents for GV3000SE
Page 2: ......
Page 4: ......
Page 5: ...GV3000 SE Power Units Instruction Manual User Manual 49 1327e 11...
Page 6: ......
Page 8: ......
Page 77: ......
Page 80: ......
Page 86: ...2 2 GV3000 SE 49 1329 e...
Page 94: ...3 8 GV3000 SE 49 1329 e...
Page 134: ...4 40 GV3000 SE 49 1329 e...
Page 188: ...7 10 GV3000 SE 49 1329 e...
Page 196: ...8 8 GV3000 SE 49 1329 e...
Page 197: ......