5 - V/HZ REGULATION MODE
49'1329 e
GV3000/SE
5 - 5
H.004
Slip Compensation
Parameter Range:
0.0% - 10.0% of Motor Nameplate Base Frequency (H.001)
Initial Setting:
0.0% (no slip compensation)
Type:
Tuneable (at rest or during operation)
Refer to:
P.095 Power Unit Output Amps
H.001 Motor Nameplate Base Frequency
Description:
This parameter is used to improve motor speed regulation by increasing the output
frequency applied to the motor (the percentage of frequency rise at Power Unit
Output Amps (P.095)).
The level of increased output frequency is a function of the value entered in H.004 (Motor
Nameplate Amps) and actual motor current.
Actual motor shaft speed is determined by two factors: inverter output frequency and the slip of the
motor. The speed reference is converted into output frequency. Motor slip is determined by the
type of induction motor and varies with load.
If the parameter is set to zero, motor speed will not be proportional to speed reference, but will
vary depending on load.
‘Slip compensation’ measures inverter output current and (at rated load) increases the output
frequency by the percentage entered in H.004. Below rated load, slip compensation will increase
inverter output frequency by the percentage in H.004 multiplied by the percent of rated load.
At load changes, the long-term speed behavior of the motor is greatly improved through the use of
this parameter.
To calculate the value entered for H.004, use the following equation:
100 * (Synch. RPM -Nameplate RPM)
Power Unit Output Amps (P.095)
H.004 = ---------------------------------------------
*
--------------------------------------------
Synchronous RPM
(Total) Motor(s) Nominal Current
Synchronous RPM = 120 * Frequency / number of Motor Poles
Example :
V/Hz mode, 2kHz, 2 motors paralleled, 1435 RPM,
Sum of 2 motor currents = 50% Power Unit Output Amps (P.095)
H.004 =100 *(1500-1435) *100% = 8.67%
1500
50%
H.005
DC Braking enable
Parameter Range:
OFF – Disable DC Braking
ON – Enable DC Braking
Initial Setting:
OFF
Type:
Tuneable (at rest or during operation)
Refer to:
P.025 Stop Mode
H.006 DC Braking Start Frequency
H.007 DC Braking Current
H.008 DC Braking Time
H.017 Input Power/Snubber Configuration
Description:
This parameter enables or disables DC Braking.
DC Braking is used to provide additional motor braking (by DC current flow through
motor windings) at speeds below Braking Start Frequency (H.006).
If DC Braking is required, DC Braking functions (H.008, H.007) must be >zero (0).
When the motor decelerates to the pre-set DC Braking Start Frequency (H.006), the
DC Braking Current (H.007) is applied to the motor after a power module-
dependent delay time. However, if parameter H.017 is set to 1 or 5, then there is no
delay for DC Braking Time (H.008).
NOTE:
This function will
not
provide holding torque as a mechanical brake. D-C-braking is
only operative when Stop Mode Selection (P.025) is set to 1 (Ramp to rest stop).
Summary of Contents for GV3000SE
Page 2: ......
Page 4: ......
Page 5: ...GV3000 SE Power Units Instruction Manual User Manual 49 1327e 11...
Page 6: ......
Page 8: ......
Page 77: ......
Page 80: ......
Page 86: ...2 2 GV3000 SE 49 1329 e...
Page 94: ...3 8 GV3000 SE 49 1329 e...
Page 134: ...4 40 GV3000 SE 49 1329 e...
Page 188: ...7 10 GV3000 SE 49 1329 e...
Page 196: ...8 8 GV3000 SE 49 1329 e...
Page 197: ......