4 - GENERAL PARAMETERS, DESCRIPTION
4 - 16
GV3000/SE
49'1329 e
P.016
Draw Gain Percentage
Parameter Range:
-100.0% to +100.0% (1.0 = 1% of speed reference)
Initial Setting:
0.0
Type:
Tunable (at rest or during operation)
Description:
This parameter is used to increase or decrease the selected speed reference to the
speed regulator by a percentage value of speed reference. (See Figure 4-4.)
It allows multiple drive sections with a common line reference, but with different
values for draw gain, to run at different speeds depending on the percent draw.
Note that P.016 affects the accel/decel times. As draw gain increases positive, the
accel/decel time decreases proportionately. As draw gain increases negative, the
accel/decel time increases proportionately. This is based on the following formula:
Modified Accel/Decel = Accel/Decel x [1 / (1.00 + (Draw% / 100))]
P.017
Acceleration Time 2 (RAMP 2)
Parameter Range:
1.0 - 999.9 seconds (V/Hz) or 0.1 - 999.9 seconds (Vector)
Initial Setting:
20.0
Type:
Tunable (at rest or during operation)
Refer to:
P.001 Acceleration Time 1
P.007 Terminal Strip Digital Inputs Configure
Description:
This parameter sets the acceleration time when a second ramp selection is
configured as a digital input. Acceleration time in which the motor ramps from zero
to Motor Top Speed (Vector: U.017) or Maximum Hz (V/Hz: P.004) after starting.
When RAMP 2 acceleration time digital input is asserted, the RAMP 2 deceleration
time also takes effect.
If the motor load inertia is high or the current limit (P.005) setting is too low, actual
motor acceleration time will be longer than the time set in P.017.
The time the motor takes to make any speed decrease is directly proportional to the
value in this parameter. This parameter does not apply if Jog is selected.
P.018
Deceleration Time 2 (RAMP 2)
Parameter Range:
1.0 - 999.9 seconds (V/Hz)
0.1 - 999.9 seconds (Vector)
Initial Setting:
20.0
Type:
Tunable (at rest or during operation)
Refer to:
P.002 Deceleration Time 1
P.007 Terminal Strip Digital Inputs Configure
Description:
This parameter sets the deceleration time when a second ramp selection is
configured as a digital input. When RAMP 2 deceleration time digital input is
asserted, the RAMP 2 acceleration time also takes effect.
Deceleration time is the time in which the motor decreases from Motor Top Speed
(Vector: U.017) or Maximum Hz (V/Hz: P.004) to zero speed when performing a
ramp stop (P.025 =1).
The time the motor takes to make any speed decrease (except a coast-to-rest stop)
is directly proportional to the value in this parameter.
This parameter does not apply if Jog is selected.
Summary of Contents for GV3000SE
Page 2: ......
Page 4: ......
Page 5: ...GV3000 SE Power Units Instruction Manual User Manual 49 1327e 11...
Page 6: ......
Page 8: ......
Page 77: ......
Page 80: ......
Page 86: ...2 2 GV3000 SE 49 1329 e...
Page 94: ...3 8 GV3000 SE 49 1329 e...
Page 134: ...4 40 GV3000 SE 49 1329 e...
Page 188: ...7 10 GV3000 SE 49 1329 e...
Page 196: ...8 8 GV3000 SE 49 1329 e...
Page 197: ......