Single Interlock Preaction, New York City
Custom Program
1. Apply power to the panel.
2. Slide the program switch down.
3. Press the FUNCTION button until the display reads “PASS-
WORD=000.”
4. To enter a password, press the SELECT button until the proper
number is displayed above the “^” symbol; then press the SET
button to move to the next digit. After entering the third num-
ber, the display will change (All panels are shipped with a “000”
password).
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##” (the second “#” character refers to the current
program number between “0” and “24”).
6. Press the SELECT button until the display reads “PROGRAM
#6.”
7. Press the SET button.
8. Slide the program switch up.
9. Slide the program switch down.
10. Repeat steps 3 to 5, then proceed to step 11.
11. Press the SELECT button until the display reads “PROGRAM
#0.”
12. Press the SET button.
13. Press the FUNCTION button until the display reads “OUTPUT
1: INDICATING.”
14. Press the SET button until the display reads “OUTPUT #2: IN-
DICATING.”
15. Press the SELECT button until the display reads “TROUBLE
BELL.” Press the SET button.
16. Press the FUNCTION button until the display reads “ZONE 1
OUTPUTS.” The “v” is pointing to the first available output for
the zone indicated on the display. If the number is displayed, it
is turned on for that zone. If the number is not displayed, the
zone is turned off.
17. Press the FUNCTION button until the display reads “ZONE 3
OUTPUTS.”
18. Press the SELECT button. The “1” should appear under the
“v”.
19. Press the SET button twice. The panel is completely pro-
gramed except for the custom banner and zone messages. If
these messages are not desired, then slide the program switch
back up.
INPUTS:
1 conventional zones, 1 manual release zone, 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUTS:
1 general alarm bell, 1 trouble bell, 1 supervisory bell, and 1 solenoid release circuit.
OPERATION: Activation of either the conventional zone or the manual release (or operation of the manual pull station
within the PrePak cabinet) will operate the solenoid release
circuit and the general alarm bell.
Activation of the waterflow zone will operate the general alarm bell.
Activation of either the low air zone or the supervisory zone will operate the supervisory bell.
A trouble condition (low battery, wiring problem, etc.) will operate the trouble bell.
When either Zone #1 or #2 is in alarm, Output #1 (general alarm) and Output #4 (solenoid release)
will operate.
When Zone #3 is in alarm, Output #1 (alarm bell) will operate.
When either Zone #4 or the supervisory zone is activated, Output #3 (supervisory bell) will operate.
When the panel is in a trouble condition, Output # 2 (trouble bell) will operate.
Note:
(1)
The Butterfly valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC Releasing/
Control panel
(2)
The emergency manual release within the PrePak cabinet is wired into the conventional detection zones 1 and 2, and is
designed to release the solenoid for setup and testing purposes.
For additional Information, please refer to the “Installation, Operation, and Instruction Manual” for the Potter
PFC4410-RC Releasing Control Panel (provided with the unit).
CUSTOM NYC PROGRAM
OUTPUTS
ZONES
Supervisory 2
(1)
#1
Conventional
(2)
#2
Conventional
(2)
#3
Waterflow
#4
Low Air Supervisory
#1 ALARM
X
X
#2 TROUBLE
Panel trouble condition is mapped to Output #2 (Trouble Bell) for NYC
#3 SUPERVISORY
X
X
#4 RELEASE
X
20.
Summary of Contents for N2-Blast DDX
Page 3: ...Fig 1 3 ...
Page 8: ...Fig 2 8 ...
Page 9: ...Fig 3 9 ...
Page 10: ...10 Fig 4 ...
Page 11: ...11 Fig 5 ...
Page 12: ...Fig 6 12 ...
Page 13: ...13 Fig 7 ...
Page 14: ...Fig 8 Wiring Diagram 14 ...
Page 15: ...15 Fig 9 Wiring Diagram ...
Page 25: ...Fig 10 Nitrogen Generator Filter Locations 25 ...