Double Interlock Preaction, Single Zone Detection
Potter Program #9
1. Apply power to the panel.
2. Slide program switch down.
3. Press the FUNCTION button until display reads “PASS-
WORD=000.”
4. To enter a password, press the SELECT button until the prop-
er number is displayed above the “^” symbol; then press the
SET button to move to the next digit. After entering the third
number, the display will change. (All panels are shipped with a
“000” password).
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##.” (the second “#” character refers to the current
program number between “0” and “24”).
6. Press the SELECT button until the display reads “PROGRAM
#9.”
7. Press the SET button.
8. The panel is completely programmed except for the custom
banner and zone messages. Slide the program switch back
up.
INPUTS: 1 supervisory zone, 1 conventional detection zone, 1 low air supervisory zone, 1 waterflow zone, 1 low air
alarm zone.
OUTPUTS:
1 general alarm, 1 supervisory, 1 waterflow, 1 solenoid release circuit.
OPERATION: Activation of the conventional detection zone and the low air alarm zone at the same time (or operation of
the manual pull station within the PrePak cabinet) will operate the solenoid release circuit and the general
alarm bell.
Activation of the conventional zone only will operate the general alarm output.
Activation of the low air supervisory zone will operate the supervisory bell output.
Activation of the waterflow zone will operate the waterflow bell output.
Activation of the low air alarm zone will operate the supervisory bell output. It will not operate the alarm
relay.
When Zone #1 is in alarm, Output #1 will operate.
When Zone #2 is activated, Output #3 will operate.
When Zone #3 is in alarm, Output #2 will operate.
When Zone #4 is activated, Output #3 will operate. This will create a supervisory condition not an alarm
condition. The alarm relay will not operate, the supervisory relay will.
When both Zones #1 and #4 are activated at the same time, the solenoid circuit will operate.
Note:
(1)
The Butterfly valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC Releasing/
Control panel
(2)
The emergency manual release within the PrePak cabinet is wired into the conventional detection zones 1 and 2, and is
designed to release the solenoid for setup and testing purposes.
For additional Information, please refer to the “Installation, Operation, and Instruction Manual” for the Potter
PFC4410-RC Releasing Control Panel (provided with the unit).
POTTER PROGRAM #9
OUTPUTS
ZONES
Supervisory 2
(1)
#1
Conventional
(2)
#2
Conventional
(2)
#3
Waterflow
#4
Low Air Alarm
#1 ALARM
X
#2 WATERFLOW
X
#3 SUPERVISORY
X
X
#4 RELEASE
XX
XX
18.
Summary of Contents for N2-Blast DDX
Page 3: ...Fig 1 3 ...
Page 8: ...Fig 2 8 ...
Page 9: ...Fig 3 9 ...
Page 10: ...10 Fig 4 ...
Page 11: ...11 Fig 5 ...
Page 12: ...Fig 6 12 ...
Page 13: ...13 Fig 7 ...
Page 14: ...Fig 8 Wiring Diagram 14 ...
Page 15: ...15 Fig 9 Wiring Diagram ...
Page 25: ...Fig 10 Nitrogen Generator Filter Locations 25 ...