Should the vessel surface thermocouple output reach the high temperature alarm/heater cutout
setting, power to the oil heater element is interrupted. When this happens the oil temperature as
indicated on the heater controller display will begin to decrease. As the oil temperature falls below
oil heater controller setting, the heater controller will sense the decreasing oil temperature and
attempt to energize the heater. However the high limit controller will prohibit the oil heater from
energizing and oil temperature will continue to fall. The Heater On pilot light will be illuminated
because the heater controller is providing an ON signal to the heater power control relay.
NOTICE:
When a Heater High Temperature alarm occurs the red
press-to-test pilot light will illuminate. The alarm pilot light
will remain illuminated and the oil heater will not be
operable until the press-to-test Heater High Temperature
reset button is depressed. Press to resume heater
operation.