Regency HZ33CE Gas Fireplace
17
INSTALLATION
Wherever necessary due to
external location of cap, the
AstroCap can be replaced
with the FPI Riser Vent Ter-
mination Cap.
REGENCY
®
DIRECT VENT FLEX SYSTEM
Horizontal Terminations Only
This venting system, in combination with the HZ33CE-4 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey.
The location of the termination cap must conform to the requirements in the "Exterior Vent Terminal Locations" Section .
Regency
®
Direct Vent Flex Termination Kit (Part # 946-513. includes all the parts needed to install the HZ33CE with a maximum run of 2 feet.
If
installing the HZ33CE-4 with a
continuous
vent length of more than 2 ft (.6m) to a maximum of 10 ft. (3.0m) use Kit # 946-515 (4 ft) or 946-516 (10 ft) or
see "Rigid Pipe Venting Systems" Section for alternate venting arrangements.
MINIMUM
FLEX KIT CENTER-LINE
MINIMUM
RIGID PIPE CENTER-LINE
AstroCap Flex Kits
1
6-7/8" dia. fl exible liner (kit length)
2
4" dia. fl exible liner (kit length)
3
spring spacers (3.
4
thimble (2.
5
AstroCap termination cap (1.
6
screws (12.
7
tube of Mill Pac (1.
8
plated screws (8.
9
screws #8 x 1-1/2" drill point,
stainless steel (4.
Notes:
1. Liner sections should be continuous
without any joints or seams.
2. Only Flex pipe purchased from Regency
®
may be used for Flex installations.
Alternate
Horizontal
Termination
Caps
Note:
- Unit must be raised by 1".