14
Regency HZ33CE Gas Fireplace
INSTALLATION
M
L
K
P Q
O
N
Opening for gas
connection
J
I
Floor
DETAIL N
SCALE 1 : 6
2X4 HEADER
N
Non-combustible
Header
(steel stud
on edge)
G
H
I
J
Framing Dimensions
Description
HZ33CE
G
Framing Width
35"(889mm)
H
Framing Height *
31-3/4" (806mm)
I
Framing Rise from Floor
0" (when not using a surround)
2" min (when using Mantel)
3-5/16" min (when using 4 sided Faceplate)
J * For Finish with Tile
Surround
Framing Depth Vertical
Horizontal
22-3/4" (578mm)
Vertical Rise
19-3/4" (502mm)
Rigid
/ 16" (406mm)
Flex
K
Corner Wall Length
38-15/16" (988mm)
L
Corner Facing Wall Width
55-1/2" (1410mm)
M
Framed Chase Ceiling*
36" (914mm)
Rigid
32" (812mm)
Flex
N
Vent Centerline Height*
30" (762mm)
Rigid
26" (660mm)
Flex
O
Gas Connection Height*
1 1/2" (38mm)
P
Gas Connection Inset*
7-3/16" (183mm)
Q
Gas Connection Width*
3" (76mm)
FRAMING DIMENSIONS
NOTE:
If this is an outside corner, the
minimum distance between the vent
and the outside corner is 6" (15cm)
with AstroCap termination cap or 12"
(30cm) with Rigid Vent termination
cap.
(For example Dura-Vent)
* Measured from base of unit.