City Series
|
53
installation
Vertical Terminations
Rigid Pipe 4" x 6-5/8
"
• Two 45
o
elbows equal to one 90
o
elbow. Maximum of six 45
o
elbows allowed.
•
Vent must be supported at offsets.
• Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each loor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994. when using rigid pipe vent systems
)
Vertical Venting with Three (3) 90
o
Elbows
One 90
o
elbow = Two 45
o
elbows.
V
H1
H
V1
Option
V
H + H1
V + V1
With these options,
max. total pipe length
is 30 feet with min. of
10 feet total vertical
and max. 8 feet total
horizontal.
Please note min. 1
foot between 90
o
elbows is required.
A)
1' Min.
2' Max
3' Min.
B)
2' Min.
3' Max
4' Min.
C)
3' Min.
4' Max
6' Min.
D)
4' Min.
5' Max
7' Min.
E)
5' Min.
6' Max
8' Min.
F)
6' Min.
7' Max
9' Min.
G)
7' Min.
8' Max
10' Min.
Lengths do not include elbow indicated
Summary of Contents for City Series CB40E-LP
Page 86: ...86 City Series parts list 7 8 9 2 1 3 6 4 5 12 17 27 19 20 18 22 6a 26 24 23 25 11 ...
Page 89: ...City Series 89 parts list 16 12 22 21 18 20 19 9 26 25 8 11 26 16 16 6 23 5A 27 17 16 ...
Page 90: ...90 City Series notes ...
Page 95: ......
Page 96: ...96 City Series notes ...
Page 97: ...City Series 97 notes ...
Page 98: ...98 City Series notes ...
Page 99: ......