58 |
City Series CB40E-12
installation
Notes:
1. Liner sections should be continuous without any joints
or seams.
2. Only Flex pipe purchased from Regency
®
may be used
for Flex installations.
3. Horizontal vent must be supported every 3 feet.
4. Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer runs
are required, rigid pipe must be used.
Horizontal Terminations - Flex Vent 4" x 6-7/8" (102mm x 175mm)
These venting systems, in combination with the CB40E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock
Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination
Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the CB40E using a flexible vent.
FPI Kit #
Length Contains:
#946-513
2 Feet
1.
6-7/8” (178 mm) flexible outer liner (Kit length)
2.
4” (102 mm) flexible inner liner (Kit length)
3.
spring spacers
4.
thimble
5.
AstroCap
termination cap
6.
screws
7.
tube of Mill Pac
8.
plated screws
9.
S.S. screws #8 x 1-1/2” (38mm) drill point
#946-515
4 Feet
#946-516
10 Feet