54
|
Grandview
®
G600C-1 Gas Fireplace
installation
V1
H1
H
V
Horizontal Terminations - Two 90°Elbows
H
H1
V
One 90
o
elbow = Two 45
o
elbows.
Option V
H + H1
With these options, maximum
total pipe length is 30 feet with
minimum of 6 feet total vertical
and maximum 8 feet total
horizontal.
Please note minimum 1
foot between 90
o
elbows is
required.
A)
0' Min.
2' (0.61m) Max.
B)
1' (0.3m) Min.
3' (0.91m) Max.
C)
2' (0.61m) Min.
4' (1.22m) Max.
D)
3' (0.91m) Min.
5' (1.52m) Max.
E)
4' (1.22m) Min.
6' (1.82m) Max.
F)
5' (1.52m) Min.
7' (2.13m) Max.
G)
6' (1.82m) Min.
8' (2.44m) Max
Restrictor Set #1 - 2" (51mm) open. Lengths do not include elbows indicated.
*Required when using rigid venting.
Horizontal Terminations - Three 90
o
Elbows
One 90
o
elbow = Two 45
o
elbows.
Option
V
H
V + V1
H + H1
With these op-
tions, max. total
pipe length is 30
feet with min. of 12
feet total vertical
and max. 9 feet
total horizontal.
Please note min.
1 foot between
90
o
elbows is
required.
A)
0' Min.
1' (0.3 m) Max.
1' (0.3 m) Min.
2' (0.61 m) Max.
B)
1' (0.3 m) Min.
2' (0.61 m) Max. 3' (0.91 m) Min.
3' (0.91 m) Max.
C)
2' (0.61 m) Min.
2' (0.61 m) Max. 5' (1.52 m) Min.
4' (1.22 m) Max.
D)
3' (0.91 m) Min.
2' (0.61 m) Max. 7' (2.13 m) Min.
5' (1.52 m) Max.
E)
4' (1.22 m) Min.
3 (0.91 m) Max.
9' (2.74 m) Min.
6' (1.82 m) Max.
F)
5' (1.52 m) Min.
4' (1.22 m) Max. 10' (3.04 m) Min. 7' (2.13 m) Max.
G)
6' (1.82 m) Min.
5' (152 m) Max.
11' (3.35 m) Min. 8' (2.44 m) Max.
H)
7' (2.13 m) Min.
6' (1.82 m) Max. 12' (3.66 m) Min. 9' (2.74 m) Max.
Restrictor Set #1 - 2" (51mm) open. Lengths do not include elbows included.
*Required when using rigid venting
*
*