46
|
Grandview
®
G600C-1 Gas Fireplace
installation
Venting Introduction
The G600C-1 uses the "balanced flue" technology Co-Axial system. The
inner liner vents products of combustion to the outside while the outer liner
draws outside combustion air into the combustion chamber thereby eliminat-
ing the need to use heated room air for combustion and losing warm room
air up the chimney.
Note:
These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of
the building, and never be attached to a chimney serving a separate solid fuel
or gas burning appliance. Each direct vent gas appliance must use it's own
separate vent system. Common vent systems are prohibited.
Vent Restrictor Installation (Part # 776-027)
Diagram 2: Vent restrictor located on top exhaust assembly
1. Determine the venting configuration.
2. Go to venting arrangements section (in the manual) to determine if
a vent restrictor setting is required. (If required, proceed to Step 3).
3. Loosen the two screws that secure the top heat deflector and remove
top heat deflector (diagram 1).
4. Align the vent restrictor plate (found in the manual package) to the re-
quired vent restrictor position, per the diagrams below.
5. Once the vent restrictor plate is in the required position, secure with
2 - 1/4" x 1/2" screws. Ensure all screws are tight.
Diagram 1: Top baffle
Set 2, 1-3/4" (44mm)
open
Set 5, 1" (25mm) open
Set 3, 1-1/2" (38mm) open
Set 4, 1-1/4" (32mm) open
Restrictor plate for Set 1, 2" (51mm)
open
Restrictor Plate