36
|
Regency
®
CLASSIC™ C34-11 Direct Vent Freestanding Gas Stove
|
36
installation
SYSTEM DATA
(For 0 to 4,500 feet altitude)
Orifice Sizes:
Burner
Natural Gas #36
Burner
Propane
#52
Max. Input Rating
Natural Gas
32,000 Btu/h
Propane
29,000 Btu/h
Min. Input Rating
Natural Gas
21,000 Btu/h
Propane
23,000 Btu/h
Supply Pressure
Natural Gas
min.
5.0" w.c
max.
14.0" w.c.
Propane
min.
11.0" w.c.
max.
14.0" w.c.
Manifold Pressure High
Natural Gas
3.5" w.c.
Propane
10" w.c.
Manifold Pressure Low
Natural Gas
1.6" w.c.
Propane
6.4" w.c.
Electrical: 115V_60 Hz less than 2 amp
Circulation Fan: 75/125 CFM.
Log Set: Ceramic fiber, 4 per set.
Output capacity:
The efficiency rating of the appliance is a
product thermal efficiency rating determined
under continuous operating conditions and
was determined independently of any installed
system.
GAS CONNECTION
The gas connection is a 3/8" x 18" long flexible pipe.
This is supplied and installed at the left rear of the
unit. See "Unit Dimensions" section for Diagram.
The gas line can be rigid pipe or to make installation
easier, use a listed flexible connector and manual
shutoff valve if allowed by local codes, or copper
if approved. For minimum and maximum supply
pressure see the System Data table.
Note: During any pressure testing of the gas
supply piping system that exceeds
test pressures of 1/2 psig, this appli
-
ance and its individual shutoff valve
must be disconnected from the piping
system. If test pressures equal to or
less than 1/2 psig are used then this
appliance must be isolated from the
piping system by closing its individual
manual shutoff valve during the test
-
ing.
HIGH ELEVATION
This unit is approved in Canada for altitude 0 to
4500 ft. (CSA 2.17-2017) with the orifice supplied.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" (# 7) and/or "OUT" (# 7)
pressure tap(s), turning counterclockwise with
a 1/8" wide flat screwdriver.
3. Attach manometer to "IN" and/or "OUT" pres
-
sure tap(s) using a 5/16" ID hose.
4. Light the pilot and turn the valve to "ON" posi
-
tion.
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
7. When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Screw should be snug, but do not over
tighten.