CLASSIC™ C34-11 Direct Vent Freestanding Gas Stove
|
28
installation
Horizontal Venting with Two (2) 90
o
Elbows
Vertical Venting with Two (2) 90
o
Elbows
One 90
o
elbow = Two 45
o
elbows.
One 90
o
elbow = Two 45
o
elbows.
Option V
H
V + V1
A) 1' Min. 4' Max. 2' Min.
B) 2' Min. 5' Max. 3' Min.
C) 3' Min. 6' Max. 4' Min.
D) 4' Min. 7' Max. 5' Min.
E) 5' Min. 8' Max. 6' Min.
With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and max.
8 feet total horizontal.
Please note min. 1 foot
between 90
o
elbows is
required.
Vent restrictor position C (fully open), refer to "Vent Restrictor
Position" section
Lengths do not include elbow indicated.
Option
V
H + H1
A)
4' Min.
6' Max.
B)
5' Min.
7' Max.
C)
6' Min.
8' Max.
With these options, maximum total pipe length
is 30 feet with minimum of 6 feet total vertical
and maximum 8 feet total horizontal.
Please note minimum 1 foot between
90
o
elbows is required.
Lengths do not include elbow indicated.
Vent restrictor position C (fully open), refer to
"Vent Restrictor Position" section.