Installation
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
English — 31
The following descriptions apply to standard systems and are limited to the necessary user-provided connections.
1. Shut down the system and secure it against unintentional reactivation.
2. Remove the covers.
DANGER – electric shock! Risk of serious injury or death due to electric shock. Some parts of the device's circuit board may still
carry 230 V voltage even with the device physically isolated from the power supply. Before you remove the covers, completely
isolate the device controller from the power supply. Verify that the main circuit board is voltage-free.
3. Insert a suitable screwed cable gland for the cable bushings at the rear of the connection component. M16 or M20, for example.
4. Thread all cables to be connected through the cable glands.
5. Connect all cables as shown in the terminal diagrams.
– Connection component, see chapter 6.5.1 "Terminal plan, connection component" on page 32 .
– Operating component, see chapter 6.5.2 "Terminal plan, operating unit" on page 34 .
– Note the connection ratings of the device for the user-supplied fusing, see chapter 5 "Technical data" on page 18 .