Controller
60 — English
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
9.4.2
Service menu
This menu is protected with a password. It can be accessed only by the Reflex Customer Service. A partial summary of the settings stored
in the Service menu is proved in the Chapter Default settings, see chapter 9.4.3 "Default settings" on page 60 .
9.4.3
Default settings
The device controller is shipped with the following default settings. Use the Customer menu to adjust these values to local conditions. In
specific cases, it is possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Remarks
Language
EN
Display language
Servitec
Magcontrol
For systems with diaphragm-type pressure expansion
tank
Minimum working pressure P
0
1.5 bar
Only Magcontrol
Safety valve, pressure
3.0 bar
Pressure value for the safety valve of the heat generator
in the system to trip
Next maintenance
12 months
Time left to the next due maintenance
Floating alarm contact
YES
All messages from the Messages list are displayed
Make-up
Maximum make-up quantity
0 Litres
Only if controller with "With water meter yes"
Maximum make-up time
20 minutes
Magcontrol
Maximum make-up cycles
3 cycles within 2 hours
Magcontrol
Degassing
Degassing programme
Continuous degassing
Continuous degassing time
24 hours
Softening (Only if "With softening yes")
Lock make-up
No
In the case of soft water residual capacity = 0
Hardness reduction
8°dH
= Target – Actual
Maximum make-up quantity
0 Litres
Attainable make-up quantity
Soft water capacity
0 Litres
Attainable water capacity
Cartridge replacement
18 months
Replace cartridge
Service menu
Parameter
Setting
Remarks
Make-up
Pressure differential, "NSP" make-up
0.2 bar
Only Magcontrol
Pressure differential, filling pressure PF – P
0
0.3 bar
Only Magcontrol
Maximum filling duration
10 h
Only Magcontrol
Degassing
Idling times between degassing intervals
10 hours
Idling times between the degassing intervals
Number of degassing cycles for each
interval
n = 8
Number of degassing cycles in one interval
Daily start
08:00 h
Start of the daily degassing intervals