Operation
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
English — 49
8.1.3
Stop mode
Except for the display of information, the device is non-functional in Stop mode. Function monitoring is stopped.
The following functions are deactivated:
•
The pump is switched off.
•
The 2-ways motor ball valve in the overflow line is closed.
•
The 3-ways motor ball valve in the make-up line is closed.
To start the Stop mode, proceed as follows:
•
Touch "STOP".
Servitec 35
System
NSP
2.2 bar
Continuous degassing
Note!
The system returns an alarm if the Stop mode is activated for more than 4 hours.
– If "Floating alarm contact?" in the Customer menu is set to "Yes", the system outputs the alarm to the group alarm
contact.
8.1.4
Summer operation
If you have placed the plant system circulating pumps out of service during the summer, no degassing of the plan system water occurs.
Proceed as follows:
•
In this case, use the Customer menu to select the "Make-up degassing" degassing programme.
•
After Summer, select the "Interval degassing" degassing programme in the Customer menu or "Continuous degassing", if required.
To start Summer operation, proceed as follows:
•
Touch "Make-up degassing".
Settings > Customer > Degassing
(010) Degassing programme
Continuous degassing
Interval degassing
Make-up degassing
2.2 bar
Continuous degassing
Note!
For a detailed description of the selection of degassing programmes, see chapter 7.8 "Setting the degassing programme
in the Customer menu" on page 45 .