background image

-8-

Drawing No. LP0749 

Released 2018-01-16

The Low Update Time is the minimum amount of time between 

display updates for the Rate display. Values of 0.1 and 0.2 seconds will 

update the display correctly but may cause the display to appear 

unsteady.

RATE LOW UPDATE TIME (DISPLAY UPDATE)

 

to

  

seconds

The High Update Time is the maximum amount of time before the 

Rate display is forced to zero. (For more explanation, refer to Input 

Frequency Calculation.) The High Update Time 

must

 be higher than the 

Low Update Time and higher than the desired slowest readable speed 

(one divided by pulses per second). The factory setting of 2.0, will force 

the display to zero for speeds below 0.5 Hz or a pulse every 2 seconds.

RATE HIGH UPDATE TIME (DISPLAY ZERO)

 

to

  

seconds









5.2  MoDule 2 - r

ate

 s

etuP

 P

araMeters

 (



)

PAR

 

Rate Scaling 

Display Value

Rate Decimal 

Point

Rate 

Enable

Rate Input 

Scaling Style

Rate High 

Update Time

Rate Scaling 

Input Value

Rate Low 

Update Time

PARAMETER MENU

RATE ENABLE

This parameter enables the Rate display. For maximum input 

frequency, Rate Enable should be set to 



 when not in use. When set 

to 



, the remaining rate parameters are not accessible.

This selects the decimal point position for the rate display. This 

parameter does not affect rate scaling calculations.

RATE DECIMAL POINT











RATE SCALING INPUT VALUE

RATE SCALING DISPLAY VALUE

Enter the desired Rate Display value. This value is entered using the 

front panel buttons for either Scaling Style.*

Enter the corresponding Rate Input value using the Scaling Style 

selected.

 

to

 

 

to

 

*For value entry instructions, refer to selection/value entry in the 

Programming The Meter section.















RATE INPUT SCALING STYLE

If a Rate Input value (in Hz) and the corresponding Rate Display value 

are known, the Key-in (



) Scaling Style can be used. This allows rate 

scaling without the presence of a rate input signal.

If the Rate Input value has to be derived from the actual rate input 

signal, the Apply (



) Scaling Style should be used.













SCALING FOR RATE INDICATION

To scale the Rate, enter a Scaling Display value with a corresponding 

Scaling Input value. These values are internally plotted to a Display 

value of 0 and Input value of 0.0 Hz. A linear relationship is formed 

between these points to yield a rate display value that corresponds to 

the incoming input signal rate. The meter is capable of showing a rate 

display value for any positive slope linear process.

SCALING CALCULATION FOR KEY-IN STYLE

If a display value versus input signal (in pulses per second) is known, 

then those values can be entered into Scaling Display (



) and 

Scaling Input (



). No further calculations are needed.

If only the number of pulses per ‘single’ unit (i.e. # of pulses per foot) 

is known, then it can be entered as the Scaling Input value and the 

Scaling Display value will be entered as the following:

RATE PER

DISPLAY (



)

INPUT (



)

Second

1

# of pulses per unit

Minute

60

# of pulses per unit

Hour

3600

# of pulses per unit

NOTES:

1. If # of pulses per unit is less than 1, multiply both Input and Display 

values by 10 or 100 as needed to obtain greater accuracy.

2. If the Display value is raised or lowered, then Input value must be 

raised or lowered by the same proportion (i.e. Display value for per 

hour is entered by a third less (1200) then Input value is a third less 

of # of pulses per unit). The same is true if the Input value is raised 

or lowered, then Display value must be raised or lowered by the 

same proportion.

3. Both values must be greater than 0.

EXAMPLE:

1. With 15.1 pulses per foot, show feet per minute in tenths. Scaling 

Display = 60.0 Scaling Input = 15.1.

2. With 0.25 pulses per gallon, show whole gallons per hour. (To have 

greater accuracy, multiply both Input and Display values by 10.) 

Scaling Display = 36000 Scaling Input = 2.5.

Key-in Style:

Enter the Rate Input value using the front panel buttons. This value is 

always in pulses per second (Hz).*

Apply Style:

The meter initially shows the stored Rate Input value. To retain this 

value, press 

PAR 

to advance to the next parameter. To enter a new 

value, apply the rate input signal to Input A. Press 

RST

 and the applied 

input frequency (in Hz) will appear on the display. To insure the correct 

reading, wait several rate sample periods (see Rate Low Update Time) 

or until a consistent reading is displayed. Press 

PAR

 to store the 

displayed value as the new Rate Input value. 

Summary of Contents for PAX Lite PAXLCR

Page 1: ...MARY All safety regulations local codes and instructions that appear in this and corresponding literature or on equipment must be observed to ensure personal safety and to prevent damage to either the...

Page 2: ...Both inputs allow selectable active low or active high logic and selectable input filtering for low frequency signals or switch contact debounce Input A Logic level or magnetic pickup signals Trigger...

Page 3: ...uctive loads and to minimize radiated and conducted noise EMI some type of contact protection network is normally installed across the load the contacts or both The most effective location is across t...

Page 4: ...C DC AC DC 2 1 ON 3 4 MAGNETIC PICKUP INPUT B COMMON INPUT A COMMON 4 5 6 7 5 24V EXC 3 to 2 5 mA MAX Resistor to Limit Current ON 1 2 3 4 AC 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 1 2 ON 3...

Page 5: ...his also advances the meter to the next parameter For numeric values the value is displayed with one digit flashing initially the right most digit Pressing the RST button increments the digit by one o...

Page 6: ...ut actions are shown in the boxes below For simple counting applications it is recommended to use Count with Direction for the count mode Simply leave the direction input unconnected Shaded area selec...

Page 7: ...edths Scale Factor Desired Display Units x Decimal Point Position Number of Pulses Given that 128 pulses are equal to 1 foot display total feet with a one hundredth resolution Scale Factor 1 00 x 100...

Page 8: ...ponding Scaling Input value These values are internally plotted to a Display value of 0 and Input value of 0 0 Hz A linear relationship is formed between these points to yield a rate display value tha...

Page 9: ...tensity Programming any Security Code other than 0 requires this code to be entered at the prompt in order to access Full Programming mode Quick Programming mode if enabled is accessed before the prom...

Page 10: ...e model and version x x of the meter The display then returns to Press the PAR button to exit the module VIEW MODEL AND VERSION DISPLAY Select the display to which the Setpoint is assigned SETPOINT AS...

Page 11: ...off at O1 The setting only applies if Setpoint 1 Output Action is programmed for timed output SETPOINT 2 OUTPUT OFF AT SETPOINT 1 SP2 Only High Acting Boundary Type activates the output when the assi...

Page 12: ...int Assignment Setpoint Enable Setpoint Output Action Setpoint Annunciator SP1 Only Setpoint Value Setpoint Output Time out Setpoint Output Logic Exit Programming Counter Auto Reset Setpoint Boundary...

Page 13: ...POE CUB4LP40 SLX 8ES 1 TORF1000 WF1000BF FANWAND721SMA FCOPPER SFP 100 PSDR060W SLX 5ES 1 309FXE ST 15 CRM000CMCMOD0000 CRM000CMDN000000 CR10001000000210 CR30001000000420 PAXDP000 NT24K 16M12 POE PT N...

Reviews: