EMC INSTALLATION GUIDELINES

Although Red Lion Controls products are designed with a high degree of 

immunity to Electromagnetic Interference (EMI), proper installation and wiring 

methods must be followed to ensure compatibility in each application. The type 

of the electrical noise, source or coupling method into a unit may be different 

for various installations. Cable length, routing, and shield termination are very 

important and can mean the difference between a successful or troublesome 

installation. Listed are some EMI guidelines for a successful installation in an 

industrial environment.

1. A unit should be mounted in a metal enclosure, which is properly connected 

to protective earth.

2. Use shielded cables for all Signal and Control inputs. The shield connection 

should be made as short as possible. The connection point for the shield 

depends somewhat upon the application. Listed below are the recommended 

methods of connecting the shield, in order of their effectiveness.

a. Connect the shield to earth ground (protective earth) at one end where the 

unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when 

the noise source frequency is over 1 MHz.

3. Never run Signal or Control cables in the same conduit or raceway with AC 

power lines, conductors, feeding motors, solenoids, SCR controls, and 

heaters, etc. The cables should be run through metal conduit that is properly 

grounded. This is especially useful in applications where cable runs are long 

and portable two-way radios are used in close proximity or if the installation 

is near a commercial radio transmitter. Also, Signal or Control cables within 

an enclosure should be routed as far away as possible from contactors, 

control relays, transformers, and other noisy components. 

4. Long cable runs are more susceptible to EMI pickup than short cable runs.

5. In extremely high EMI environments, the use of external EMI suppression 

devices such as Ferrite Suppression Cores for signal and control cables is 

effective. The following EMI suppression devices (or equivalent) are 

recommended:

Fair-Rite part number 0443167251 (Red Lion Controls #FCOR0000)

Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion Controls #LFIL0000)

6. To protect relay contacts that control inductive loads and to minimize radiated 

and conducted noise (EMI), some type of contact protection network is 

normally installed across the load, the contacts or both. The most effective 

location is across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide 

varistor (MOV) across an AC inductive load is very effective at reducing 

EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor 

switch, care must be taken not to exceed the breakdown voltage of the 

transistor when the load is switched. One of the most effective ways is to 

place a diode across the inductive load. Most Red Lion products with solid 

state outputs have internal zener diode protection. However external diode 

protection at the load is always a good design practice to limit EMI. 

Although the use of a snubber or varistor could be used.

Red Lion part numbers: Snubber: SNUB0000

   

Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output devices to the 

instrument. When a separate input and output common is provided, they 

should not be mixed. Therefore a sensor common should NOT be connected 

to an output common. This would cause EMI on the sensitive input common, 

which could affect the instrument’s operation.
Visit 

http://www.redlion.net/emi

 for more information on EMI guidelines, 

Safety and CE issues as they relate to Red Lion products.

Wiring Connections

All conductors should meet voltage and current ratings for each terminal. 

Also cabling should conform to appropriate standards of good installation, local 

codes and regulations. It is recommended that power supplied to the unit (AC 

or DC) be protected by a fuse or circuit breaker.

After the unit has been mechanically mounted, it is ready to be wired. All 

wiring connections are made to rear screw terminals. When wiring the unit, use 

the numbers on the label and those embossed on the back of the case, to identify 

the position number with the proper function. See page 46 for terminal 

descriptions. Strip the wire, leaving approximately 1/4” (6 mm) bare wire 

exposed (stranded wires should be tinned with solder). Insert the wire under the 

clamping washer and tighten the screw until the wire is clamped tightly.

Caution: Unused terminals are NOT to be used as tie points. Damage to the 

counter may result if these terminals are used.

-6-

Summary of Contents for C48C

Page 1: ...THE 1 16 DIN COUNTERS MODEL C48C INSTRUCTION MANUAL...

Page 2: ...on and control requirements The C48C unit which you have purchased has the same high quality workmanship and advanced technological capabilities that have made Red Lion Controls the leader in today s...

Page 3: ...ersions C48CXX1X 7 Serial Communication Wiring 8 User Inputs 8 Output Wiring 8 Input A and Input User B 8 Various Sensor Output Connections 10 FRONT PANEL DESCRIPTION 11 Keypad Functions 11 BASIC OPER...

Page 4: ...cess Preset Values 22 Preset 1 Value 22 Preset 2 Value Dual Preset Batch Models only 22 Preset 3 Value Batch Model only 22 Preset 1 Track Preset 2 Dual Preset Batch Models only 22 Access Output Time V...

Page 5: ...Chart 28 User Settings Chart 29 RS 485 SERIAL COMMUNICATIONS 30 Communication Format 30 Sending Commands and Data 30 Receiving Data 32 Serial Connections 33 Terminal Descriptions 33 Troubleshooting S...

Page 6: ......

Page 7: ...d for Program Disable and the Accessible value parameters can all be utilized to provide multi level protection against unauthorized changes to data values and unit configuration The Standard Counter...

Page 8: ...CIRCUITRY HI LO BIAS SNK SRC HI LO FREQ SW7 PROGRAM DISABLE SOLID STATE PNP CURRENT SOURCING OUTPUT S VSRC SOLID STATE NPN CURRENT SINKING OUTPUT S RELAY OUTPUT S N O USER INPUT 1 INPUT A INPUT USER B...

Page 9: ...izontal stacking the panel latch screws should be at the top and bottom of the unit The minimum spacing from center line to center line of units is 1 96 49 8 mm This spacing is the same for vertical o...

Page 10: ...rom the panel first loosen the panel latch screws Insert flat blade screwdrivers between the panel latch and the case on either side of the unit so that the latches disengage from the grooves in the c...

Page 11: ...oard connectors Be certain connectors are fully mated 4 Connect the bezel display board assembly by guiding the board ends into the bezel latches Slide the assembly on evenly until the display board c...

Page 12: ...L0000 6 To protect relay contacts that control inductive loads and to minimize radiated and conducted noise EMI some type of contact protection network is normally installed across the load the contac...

Page 13: ...AC respectively Output Power For DC Low Voltage AC units that do not have PNP current sourcing outputs Terminal 10 DC OUT VSRC IN provides a DC output for sensor power 12 VDC 15 The maximum sensor cur...

Page 14: ...s instructions for installation Note Snubber leakage current can cause some electro mechanical devices to be held ON Input A and Input User B Input A and Input B have identical circuitry and share the...

Page 15: ...alues 10 when the counter voltage at the DC OUT IN terminal is 12 VDC These typical values will vary in proportion to the variations in DC OUT IN terminal voltage caused by line voltage and load chang...

Page 16: ...C COUNT ON TURN ON CURRENT SINK CONNECTED COUNT ON CLOSING INTERFACING WITH CMOS CIRCUITRY B TYPE NOTES 1 SENSOR VOLTAGE AND CURRENT The DC OUT IN terminal can supply 12 VDC 100 mA max within a 15 ra...

Page 17: ...key is used as a quick reference for the operator if the function key is selected for a reset function This key is used to access programming enter changes to data values and scroll through the avail...

Page 18: ...grammable automatic reset modes The batch counter displays the number of process cycles that have been completed The total count is the total number of counts that have been received since the total w...

Page 19: ...P 124 200 PRS 300 3 250 124 250 CodE 000 2 PRS Prot VALuES 1 000100 PrESEt PRS 1 t 010 OutPut 2 PScALr OutPut 999999 3 Prot SAVE CodE Error 00002 PrESEt PRS 2 0 OutPut key held for 2 seconds Cnt 1 Cnt...

Page 20: ...ERMINAL PROGRAM CODE NUMBER PROTECTED VALUE MENU OPERATOR ACCESS AT MAIN DISPLAY PROGRAM DISABLE LEVEL PROGRAMMING ENABLED OFF INACTIVE or Not Programmed for Pro dis ALL No All displayed values change...

Page 21: ...key will allow changing of the value The two methods for changing numeric data values are digit entry and auto scrolling Digit Entry If the data entry method has been set to digit entry the least sig...

Page 22: ...input the display changes by 1 The prescaler value selected will affect the maximum count rate See Appendix B Specifications page 39 It is important to note that the precision of a counter applicatio...

Page 23: ...ermined by the logic state of Input B A high level at Input B causes the unit to count in a positive direction A low level causes the unit to count in a negative direction AD SUB This mode effectively...

Page 24: ...puts A and B to be counted This results in a resolution four times greater than in the basic quadrature X1 mode Counter 1 Operating Mode The charts on the following pages show operating modes for sing...

Page 25: ...4 Manual Reset to Zero 01 off at 02 02 Latched 5 Manual Reset to Zero 01 off at 02 02 Timed 6 Manual Reset to Preset 2 Latched Outputs 7 Manual Reset to Preset 2 01 Timed 02 Latched 8 Manual Reset to...

Page 26: ...ET TYPE Auto RESET To Zero To Preset 2 at Timed 02 End OUTPUT 1 Latched Timed O1 Off at O2 OUTPUT 2 Latched Timed 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 MODE Reversed Count Direction Up Dn Up Dn...

Page 27: ...med output 3 end Manual Counter can only be manually reset by a User Input or by Serial Communications command Reset to Zero When reset manually or automatically counter 2 goes to zero Output 3 is tri...

Page 28: ...ls only This parameter configures whether or not the Preset 1 value tracks or follows the Preset 2 value PRS PRS PRS PRS 2 PRS 3 PRS 2 PRS 1 MODE DESCRIPTION Locked Preset is not viewable at main disp...

Page 29: ...Output 3 Time Value controls the Output 3 duration when Output 3 is set for timed mode of operation parameter The Output time value range will be 0 01 99 99 Seconds or 0 1 999 9 seconds depending on...

Page 30: ...er up Previous State For latched output modes only The output will power up in the state it was in at power down For non latched modes the output will power up in the off state User Input State Source...

Page 31: ...ntary reset Reset All Level Active Batch model Only When the user input is activated the Counter 1 and Counter 2 values and outputs will reset and be held reset until user input is released Change Dis...

Page 32: ...400 Baud Even Parity 7 data bits 4800 Baud No Parity 8 data bits 4800 Baud Odd Parity 7 data bits 4800 Baud Even Parity 7 data bits 9600 Baud No Parity 8 data bits 9600 Baud Odd Parity 7 data bits 960...

Page 33: ...Only This parameter determines the Prescaler Output Pulse width The Prescaler Output activates on falling edges of the count signal Once activated the Prescaler Output Pulse will remain activated for...

Page 34: ...P STATE USER INPUTS USER INPUT 1 USER INPUT 2 USER INPUT B USER F1 KEY PROGRAMMING CODE VALUE SCROLL DISPLAY SERIAL BAUD RATE PARITY SERIAL UNIT ADDRESS ABBREVIATE SERIAL MNEMONICS PRINT OPTIONS PRINT...

Page 35: ...ATE SERIAL MNEMONICS SERIAL UNIT ADDRESS SERIAL BAUD RATE PARITY RS 485 SERIAL OPTION DUAL PRESET BATCH MODELS ONLY SCROLL DISPLAY PROGRAMMING CODE VALUE USER F1 KEY USER INPUT B USER INPUT 2 USER INP...

Page 36: ...be programmed to the same baud rate and parity as the connected equipment In addition the loop address number and print options should be known When used with a terminal or host computer and only one...

Page 37: ...ll units on the line after a transmit value or print request command is sent to a specific unit on the line The C48C will require a maximum of 50 msec to process the asterisk The command string is con...

Page 38: ...f transmission from a print request to provide separation between print outs If serial is abbreviated just numeric data is sent with no time delay If the C48C transmits mnemonics there is a 400 msec b...

Page 39: ...eck to make sure that the computer or device is configured with the same communication format as the C48C The communication format the C48C will accept is 1 start bit 7 or 8 data bits no parity or 1 p...

Page 40: ...85 OPTION 50 60 HZ 9VA B 1 2 14 13 A 85 250 VAC INPUT A USER INPUT 1 6 7 RS 485 OPTION 3 USER 5 4 12 11 AC AC B 1 2 13 14 A INPUT USER B 8 DC OUT IN 10 COMM 9 USER INPUT 1 INPUT A 6 7 O2 SS INPUT 2 O3...

Page 41: ...lication s Max Input Frequency 2 0 5 As a rule the counter connected to the prescaler output should be able to accept a count rate at or higher than the Effective Prescaler Output Frequency 35 Example...

Page 42: ...ft The C48CB was ordered with the RS 485 serial communication option Future plans include a data acquisition program to interrogate the C48CB s A 100 ppr rotary pulse generator is shaft coupled to a 4...

Page 43: ...37 locked PRS1 value 0 25 less than PRS2 for slow down PRS2 cut length PRS3 set high so output does not activate 1t 2t 3t APPLICATION PROGRAMMING...

Page 44: ...EMORY Nonvolatile E2PROM retains all programmable parameters and count values 4 SENSOR POWER 12 VDC 15 100 mA max 5 COUNT INPUTS A B Accepts count pulses from a variety of sources DIP switch selectabl...

Page 45: ...00001 9 0 6 1 2 1 8 2 4 1 1 2 2 7 00001 8 0 6 1 3 2 2 8 1 3 2 7 6 00001 7 0 7 1 4 2 2 3 2 1 4 2 9 5 00001 6 0 8 1 7 2 5 3 8 1 7 3 4 4 00001 5 1 2 2 8 4 4 2 4 1 3 00001 4 1 3 2 5 3 4 5 2 2 4 5 2 00001...

Page 46: ...he count speed rate 9 RS485 SERIAL COMMUNICATIONS Optional Up to 32 units can be connected Baud Rate Programmable from 1200 to 9600 baud Address Programmable from 0 to 99 Data Format 10 Bit Frame 1 st...

Page 47: ...set prescaler or output time values detected by processor 1 Data error in count values detected by processor 1 Press key 1 Press key 1 Press key 2 Check signal lines for possible noise sources 2 Check...

Page 48: ...CALER PRESETS OR OUTPUT TIME VALUES CAN BE VIEWED BUT NOT CHANGED 2 Check Front Panel Accessible Functions With Program Disable section of manual 1 Verify programming of Access parameters 1 Front pane...

Page 49: ...tion of the feed roll Each revolution equates to a linear distance of 2 feet The number of Display Units desired is 2 The Number of Pulses per Display Units is 48 When the number of Display Units and...

Page 50: ...13 3 2 B 9 10 6 8 7 USER INPUT 1 INPUT A INPUT USER B COMM DC OUT IN O3 SS O2 SS COMM USER O1 SS 12 AC 14 A RS 485 OPTION 4 5 AC 11 1 13 3 2 B 9 10 6 8 7 USER INPUT 1 INPUT A INPUT USER B COMM DC OUT...

Page 51: ...OUT AC DC AC DC 12 14 A RS 485 OPTION 4 5 11 1 13 3 2 B 9 10 6 8 7 USER INPUT 1 INPUT A INPUT USER B COMM O3 RLY O3 RLY O2 RLY O2 RLY O1 SS V IN SRC DC OUT AC DC AC DC INPUT 2 12 14 A RS 485 OPTION 4...

Page 52: ...7 C48CD017 2 Preset Counter w Prescaler Output Reflective LCD Yes No Yes N A C48CP005 C48CP015 2 Preset Counter Backlit LCD Yes No No N A C48CD100 C48CD110 2 Preset Counter Backlit LCD Yes No Yes N A...

Page 53: ...ounter Backlit LCD N A No Yes Yes O1 3 Preset Batch Counter Backlit LCD 85 to 250 VAC C48CB105 C48CB100 C48CB108 C48CB103 N A C48CB005 Yes No Yes 3 Preset Batch Counter Reflective LCD N A N A C48CB008...

Page 54: ...mer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liable for a...

Page 55: ...C48C IM G 01 17 DRAWING NO LP0354...

Page 56: ...POE CUB4LP40 SLX 8ES 1 TORF1000 WF1000BF FANWAND721SMA FCOPPER SFP 100 PSDR060W SLX 5ES 1 309FXE ST 15 CRM000CMCMOD0000 CRM000CMDN000000 CR10001000000210 CR30001000000420 PAXDP000 NT24K 16M12 POE PT N...

Reviews: