Security inspection according EN 16005
2
BAL_S20_EN_1V0_REC_121-006454590
13/ 33
If S ≤ 8 mm then t ≤ 0 mm
If S > 8 mm then t ≥ 25 mm
Figure b) Shearing and drawing-in protection
S ≤ 8 mm → Y ≤ 0 mm
S > 8 mm → Y ≥ 25 mm
Figure d) Finger protection (drawing-in)
Protective screen
See Book B5 „Options“ Chapter „Protective screen“.
This is the safest solution for protection, especially as EN 16005 recommends solutions that avoid
any contact of the doorset with the user, provided that a large proportion of the users are elderly,
disabled persons and young children.
When using a protective screen:
▪
The DIN aluminium finishing profiles are not required and rubber sealing profiles can also be
used.
▪
The safety distances for the door leaf must not be observed.
Presence sensing device
The presence sensing device IXIO-ST monitors the secondary closing edge of the door and detects
persons in the opening area of the door leaves.
However, this solution is the least user-friendly. If a person is detected within the travel area of the
doorset leaves, the door does not open or only with reduced speed, when somebody wants to go
through the doorway.
Alternatives to IXIO-ST
IMPORTANT
Only products authorised according to EN 13849-1:2006, Performance Le-
vel „c“ may be used!
Examples:
▪
IRIS ON (BEA)
▪
OA-AXIS T (OPTEX)
▪
PrimeScan (Bircher-Reglomat)
The wiring takes place on the programmable inputs of the STM or on the FEM 0 with parameterisation
of the SIO function.
Book B7 „Commissioning“ Chapter „STM 20, STM 20 DUO, STM 21, STM 22 DUO with combi-
sensors produced by third-party“ includes a table detailing the connections and settings.
General and additional requirements
Detection zone for sensor activation
Attention shall be paid to the provision and positioning of sufficient automatic activation devices (sen-
sors) for different types of doorset.
In the case of power-operated doorsets on escape routes without break-out function, the detection
zone in the escape direction shall be not less than 1500 mm measured from the centre of the opening
width of the doorset - and if possible 1000 mm for all other doors. The detection zone shall cover at
least the entire opening width of the doorset.
Solution:
Sensors must be set correctly during commissioning.
On escape routes and emergency exits, a combined sensor IXIO-DT3 must be installed on the inner
side.