Specification for fire doors
23
102-127108955
V1.1
95/ 102
Parameter setting for utilisation on fire doors
Parameter
Factory default
Change configuration to
DOOR SYSTEM
Fire alarm
Disabled
Enabled
NOTICE
For parameter setting please also see chapter
Configuration!
Hints for low-energy operators
NOTICE
The fire door and low-energy operator combination is only authorised according
to the data shown in the table below.
Arm type
Maximum authorised door closers - according to size
EN 4
EN 5
EN 6
Standard arm
authorised
not authorised
not authorised
Slide arm pulling
authorised
not authorised
Slide arm pushing
authorised
not authorised
Ü-designation
Hold-open system for bi-parting doors (master / slave)
The Master/Slave function ensures appropriate closing sequence in normal operation mode.
For the fault "power failure" a mechanical closing sequence control must always be used.
NOTICE
For parameter setting please refer to chapter
Configuration!
Acceptance of hold-open system
IMPORTANT
Acceptance, tests and maintenance should only be carried out by a specialist or
a person specifically trained for that. The authorization of these persons exclu-
sively lies with the manufacturer of the hold-open system. Extent, results and
time of the periodical inspection must be recorded. These records must be kept
by the operator.
23.4
23.5
23.6
23.7
23.7.1