Security inspection according EN 16005
3
102-127108955
V1.1
18/ 102
Additional requirements
Opening time
Doorsets shall open from closed to back check, or 80° whichever occurs first, in 3 s or longer
as required in the table below.
Closing time
The minimum closing time from 90° to 10° open (+ min. 1.5 s from 10° to 0°) shall be ad-
justed on site according to the table below. The times are to be checked with an appropriate
measuring device (e.g. stop watch).
Mass of doorset leaf (kg)
50
60
70
80
90
Width of door-
set leaf
(m)
Time (s)
0,75
3,0
3,0
3,0
3,0
3,5
0,85
3,0
3,0
3,5
3,5
4,0
1,00
3,5
3,5
4,0
4,0
4,5
1,20
4,0
4,5
4,5
5,0
5,5
Note: Values for time are rounded up to the nearest half second.
General and additional requirements
Detection zone for sensor activation
Attention shall be paid to the provision and positioning of sufficient automatic activation de-
vices (sensors) for different types of doorset.
In the case of power-operated doorsets on escape routes without break-out function, the de-
tection zone in the escape direction shall be not less than 1500 mm measured from the cen-
tre of the opening width of the doorset - and if possible 1000 mm for all other doors. The de-
tection zone shall cover at least the entire opening width of the doorset.
Solution:
Sensors must be set correctly during commissioning.
On escape routes and emergency exits, a combined sensor RIC 290 must be installed on
the inner side.
CAUTION
A combined sensor AIR 290 does not meet the 1500 mm requirement and is
consequently not allowed.