Security inspection according EN 16005
3
102-127108955
V1.1
17/ 102
Safety distances
Dimensions in millimetres
Key
1
Rubber cover
2
Rubber or textile cover
3
Profile
Safety distances in the detection field (with radar motion sensor)
Attention shall be paid to the provision and positioning of sufficient automatic activation de-
vices for different types of doorsets.
In case of swing doorsets opening against the direction of travel, a minimum depth of 1000
mm before the totally open door leaf should be observed.
Low-energy movements for swing door drive
When using a low-energy drive, in the event of any interruption of mains power or failure of
the drive, it shall be possible to open the doorset with a manual force not exceeding 67 N to
release a latch and 90 N to set the door in motion - or max. 67 N to swing the door to the ful-
ly-open position.
The force is applied to the main closing edge and is measured
vertically to its direction of travel
Annex F of standard EN 16005 states the allowable speed settings for low-energy drives.
They are calculated according to the mass of the doorset leaf and the doorset width, in
which the kinetic energy of a doorset in motion shall not exceed 1.69 J.
Low energy movement of the doorset is generally not protected with additional protective
devices.
The application of force by kinetic energy is not considered to be hazardous. However, it
should be determined according to the situation whether the residual risk is also low to eld-
erly, frail and disabled users.
For swing doorsets a static closing force up to 150 N is allowed when the gap between the
main closing edge and the counter closing edge is ≤ 8 mm.
3.1.4
3.1.5
3.1.6