Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
15
14.07.2020
"ALARM" LED
Lights when an alarm is present
"SERVICE" LED
Lights when the filter requires maintenance.
"ON" LED
Lights when the device is in operation
Does not light when the device is on the parameter selection level
Flashes when the device is on the parameter selection level
Display
To display text messages (4 x 20 characters)
5.3 Parameter selection level
To view the parameters and their values the user must switch from the operating level to the parameter
selection level. The
and
keys must be pressed simultaneously until the green “ON“ LED goes off
(approx. 3 seconds).
All parameters with their set values can now be viewed in sequence by repeatedly pressing the
or
key. Inactive or hidden parameters are automatically skipped (see section "Activated and deactivated pa-
rameters / faded in and faded out parameters" on this page).
Parameter blocks
To ensure an uncluttered view of the device’s parametrisation parameters referring to the same function
are grouped into blocks (C0, D0, E0, etc.). For example, the block D0 “
Δ
p
-controls” includes all parame-
ters (D1, D2, D3, etc.) referring to the differential pressure-dependent cleaning control (short:
Δ
p
-
controls).
Activated and deactivated parameters / faded in and faded out parameters
Two different types of parameter blocks are available: those that can be activated and deactivated and
those that can be faded in and faded out. A deactivated block is inactive. All parameters assigned to it are
without function and are not shown. With faded out parameter blocks the associated parameters are ac-
tive, that is, functioning. They are just not shown.
To activate a disabled parameter group or to fade in a faded out parameter group switching to
the parameter setting level is required (see section 5.4 "Parameter setting level" on page 17 on
this).
Parameter display examples
Parameter block C0, deactivated
Display
Meaning
Parameter block C0 "Service operating hours"
The block is inactive (deactivated)
The block is protected by Code 5
C0 Ser.ope.hours
0 inactive
Parameter code 5