Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
37
14.07.2020
Display
Meaning
Cleaning Alarm
Valve current
No pressure
No drop in pressure
Filter valv.no. ###
Ctrl.## Valv.no. ###
Row 1
Row 2
Row 2
Row 2
Row 3
Row 4
Cleaning Alarm
No valve current present or
cleaning pressure too low or
no pressure drop after a cleaning pulse
on the valve with the filter number
###
Location: I/O module RM-V6/X / RM-V8 / RM-V16 with the
control number/address
##
and the control valve No.
###
(valve connection faulty or valve defective).
RM-VXX comm.alarm
RM-VXX No. ##
No reply
Row 1
Row 2
Row 3
Row 4
RM-V6/X / RM-V8 / RM-V16 Communication alarm
Empty row
I/O module RM-V6/X / RM-V8 / RM-V16 with the address
#
sends no response
RM-VXX alarm setting
RM-VXX
Valve setting
incorrect
Row 1
Row 2
Row 3
Row 4
RM-V6/X / RM-V8 / RM-V16 Setting alarm
The valve setting of the I/O modules RM-V6/X / RM-V8 / RM-
V16 does not agree with the setting of the RM-310 C /
RM-310 CT.
Sensor alarm #
DP-Sens.defect or
Check P-connection
Row 1
Row 2
Row 3
Row 4
Sensor Alarm
#
Δ
p
-Sensor
#
defective or
Δ
p
-Connections faulty (check!)
Input Ix alarm
I < #,# mA or
not connected
Row 1
Row 2
Row 3
Row 4
Input current monitoring
Input current Ix <
#,#
mA
x = input 1, 2 or 3
#,#
= 1.00 or 3.50 mA