Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
14
14.07.2020
5 Setting procedure
5.1 Function in "as delivered" condition
The following parameters must be set before operating the RM-310 C / RM-310 CT:
E0 Cleaning control functions
EA Number of valves
EB Number of I/O modules
The RM-310 C / RM-310 CT operates automatically once the cleaning control functions, number of valves
and number of I/O modules have been set.
Cleaning starts when the filter’s differential pressure
Δ
p
has reached the "
DP-Start
" value (factory set-
ting: 1200 Pa). The solenoid valves are controlled sequentially. By cleaning the differential pressure drops
after a certain period of time. Once the differential pressure has reached the value “
DP-Start
” minus
“
DP-Hyster.
” (factory setting: 300 Pa), i.e. the differential pressure is 1200 Pa - 300 Pa = 900 Pa, clean-
ing stops.
If a different function is desired or additional functions shall be activated, the parameter setting of the
RM-310 C / RM-310 CT must be changed. See sections 5.3 "Parameter selection level" to 5.9 "Parameter
list" on this.
5.2 Operating and display elements
- key
In parameterisation mode* to select parameters or values
(in up-arrow direction)
In operating mode to call text messages not shown
(in up-arrow direction)
ENTER key
In parameterisation mode* to confirm parameters
If a service or alarm message is present, to acknowledge the
message
- key
In parameterisation mode* to select parameters and values
(in down-arrow direction)
In operating mode to call text messages not shown
(in down-arrow direction)
* the RM-310 C / RM-310 CT is on the parameter selection or parameter setting level.