Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
34
14.07.2020
Display
Meaning
Ext.cleaning on
Row 1 The input "Cleaning on" carries 1-signal at factory setting.
*
The function of the inputs can be individually set via parameter group F0-
F8. See appendix 7 "Input and output signal parametrisation, special
parameters" on this.
Cont. cleaning on
Row 1 Control released and continuous cleaning on.
F-clean.in 5 min
Row 1 Start of active forced cleaning in 5 minutes
Forced cleaning on
Row 1 Cleaning is activated after the forced cleaning time has
elapsed.
Cleaning on
Row 1 Cleaning has been activated because the rising differential
pressure of the filter has reached the value „
DP Start
“.
Cleaning off
Row 1 Cleaning has been deactivated because the dropping differen-
tial pressure of the filter has reached the value „
DP Start
“
minus „
DP Hyster.
“.
With the indicator flashing when the release of cleaning has
been requested but not granted (see parameter
Fn = 10/30 or Gn = 6/38).
The following is displayed in rows 3 and 4 in all operating
modes except in downtime:
Filter valv.no.###
Ctrl.## Valv.no.###
Row 3
Row 4
The cleaning valve with the filter number
###
is active.
Location: Control number
##
/ Control valve number
###
DP-Filter #### Pa
DP-contr. deactive
Row 2
Row 2
####
effective measured differential pressure of the filter or
parameter D0 is set to the value 0.
2
Row 2 The controller is in the 2nd downtime cycle.