A - 1
T
HE
HX2
S
ERIES
S
EMI
-I
NSTANTANEOUS
W
ATER
H
EATERS
A
PPENDIX
1
–
T
HE
C
ONTROL
M
ASTER
C
ONTROL
P
ANEL
A.1 General Operation
The function of the controller is to maintain the water outlet temperature of the water
heater and monitor its status. This is done with a PID control loop that sends a signal
to the steam control valve. Valve signaling is 0-10 VDC as standard.
Symbols shown in the border on the LCD display’s left and right borders indicate the
button functions. In the upper right corner, the “1/11” notation indicates the cursor
is at line 1 of the 11 items on this screen menu.
There are four menu levels:
MAIN
,
OPER
,
SETUP
, and
CONFIG
. The main menu
lists the primary values and access to other menus.
•
The Main menu [
MAIN
] displays the primary controller information and provides
access to the other menus.
•
The Operator menu [
OPER
] is used to select local or remote set points, adjust
the local set point, or to manually test the control valves.
•
The Setup menu [
SETUP
] is password protected and used for adjusting alarm
points or tuning the controller’s PID loop.
•
The Configuration menu [
CONFIG
] is also password protected and is used to set
up input or output signal types, ranges for variables and control valve operation.
HOME
BACK
UP
DOWN
ENTER
ALARM
Summary of Contents for HX2 Series
Page 1: ...Installation Operation and Maintenance Manual INSTALLATION OPERATION AND MAINTENANCE MANUAL ...
Page 14: ...SECTION 2 INSTALLATION HX2 SERIES 2 6 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 17: ...IOM SECTION 3 OPERATION HX2 SERIES 3 3 3 3 System Wiring Diagram Sizes 0630 and 0636 ...
Page 18: ...IOM SECTION 3 OPERATION HX2 SERIES 3 4 3 4 System Wiring Diagram Sizes 0830 Through 1236 ...
Page 39: ...IOM APPENDIX 1 THE CONTROL PANEL HX2 SERIES A 13 THIS PAGE LEFT INTENTIONALLY BLANK ...