2 SE
TTINGS
MENU
45
A
DDRESS
3 S
ETTINGS
M
ENU
/ 3.4 T
ECHNICAL
M
ENU
/ 3.4.1 P
ASSWORD
M
ENU
/ 3.4.1.1 M
AIN
/ 3.4.1.1.1 S
YSTEM
/
3.4.1.1.1.2 S
ETTINGS
/
3.4.1.1.1.2.2
W
INTER
C
OMPENSATION
S
CREENSHOT
Table of movements
Button
Screenshot
3.4.1.1.1.2.1 CLIMATE
3.4.1.1.1.2 SETTINGS
3.4.1.1.1.2.3 SUMMER COMPENSATION
SYS[1] WinComp 01
──────────────────────
Min Max Off
TExt:-05.0 20.0 0.0
TDel:45.0 22.0
──────────────────────
Winter Compensation
Curve
The parameters to be entered in the screenshot represent the characterisation of the compensation curve shown in the figure
below. The control unit, will adjust the water delivery temperature according to the outdoor temperature.
Winter Compensation Line
Reference Settings
WALL/CEILING
Name
Min
Max Name Val
TExt
-5°C
10°C
Off.
0
Del.T
48°C 36°C
FLOOR
Name
Min
Max Name Val
TExt
-5°C
20°C
Off.
0
Del.T
45°C 22°C
The parameters to be entered in the screenshot represent the characterisation of the compensation curve shown in the figure
below. The control unit will adjust the water delivery temperature according to the outdoor temperature and to the dew point.
Summer Compensation Line
Reference Settings
WALL/CEILING
Name
Min
Max Name Val
TExt
20°C 30°C
Off.
0
Del.T
16°C 12°C
FLOOR
Name
Min
Max Name Val
TExt
23°C 32°C
Off.
0
Del.T
20°C 15°C
A
DDRESS
3 S
ETTINGS
M
ENU
/ 3.4 T
ECHNICAL
M
ENU
/ 3.4.1 P
ASSWORD
M
ENU
/ 3.4.1.1 M
AIN
/ 3.4.1.1.1 S
YSTEM
/
3.4.1.1.1.2 S
ETTINGS
/
3.4.1.1.1.2.3
S
UMMER
C
OMPENSATION
S
CREENSHOT
30°C
Max External T. °C
20°C
Min External T. °C
12°C
Min Delivery T. °C
16°C
Max Delivery T. °C
T
MCL
Offset °C
“Parallel shifting”
Delivery Temp. °C
External
Temp. °C
T
MCL
= Temperature calculated through the compensation line
Table of movements
Button
Screenshot
3.4.1.1.1.2.2 WINTER COMPENSATION
3.4.1.1.1.2 SETTINGS
3.4.1.1.1.2.4 ADJUSTMENT
SYS[1] SumComp 01
──────────────────────
Min Max Off
TExt:23.0 32.0 0.0
TDel:20.0 15.0
──────────────────────
Summer Compensation
Curve
10°C
Max External T. °C
-5°C
Min External T. °C
36°C
48°C
T
MCL
Offset °C
“Parallel shifting”
External
Temp. °C
T
MCL
= Temperature calculated through the compensation line
Min Delivery T. °C
Max Delivery T. °C
Delivery Temp. °C