Table D - Alarms
1) BOILER/HEAT PUMP ALARM
BOILER ALARM
Or
HEAT PUMP
Boiler/Heat Pump lock (Winter season).
All the systems are disabled.
2) CHILLER/HEAT PUMP ALARM:
CHILLER ALARM
Or
HEAT PUMP
Chiller/Heat Pump lock (Summer season).
All the systems are disabled.
3) ROOM SENSOR ALARM:
ZONE ALARM
ROOM PROBE
Enter to view
ZONE 1
──────────────────────
Off Line:Yes
Temp. :
Humidity:- Deh:-
The presence of an error is indicated with , while its
absence with -. When the sensor is communicating, errors
in detecting Temp. (Temperature)/Humidity may occur.
The Deh (Dehumidifier) session indicates the presence of
an alarm concerning the dehumidifier serving the zone.
NB: All the functions corresponding to the type of error
are deactivated.
4) SYSTEM ALARM — ROOM TEMPERATURE SENSOR/S:
Temperature Sensor/s
Faulty-Disconnected
Enter Display
ALARM
NO ROOM TMP
──────────────────────
SYSTEM:SYST[1]
This error occurs during winter when there is no
temperature detection in the system, i.e., all the
temperature sensors connected to the system are
malfunctioning or disconnected.
NB: system Syst[1] is deactivated.
5) SYSTEM ALARM — ROOM TEMPERATURE/HUMIDITY SENSOR/S:
Temperature Sensor/s
Faulty-Disconnected
Enter Display
ALARM
DEW POINT
──────────────────────
SYSTEM:SYST[1]
This error occurs during summer when there is no
temperature/humidity detection in the system, i.e., all the
temperature/humidity sensors connected to the system
are malfunctioning or disconnected.
NB: system Syst[1] is deactivated.
The red backlight on the "Alarm" button indicates that the
control unit has detected a system failure or malfunction.
To display them, press the "Alarm" button: once pressed, the
screenshot will display all the information regarding the error.
In the event of several errors, you can scroll through them using
the UP-DOWN buttons.
To return to the control unit menu press the "Alarm" button
once again.
Below are described the possible screenshot explaining each
error.
NB: When the problem is solved, the error will no longer be
displayed when you access the alarm screenshot again. If
everything in the control unit is working properly and you
press the "Alarm" button, the screenshot indicating that
there is no ongoing alarm shall appear.
Esc
Prg
TROUBLESHOOTING