3.4.1.1.1 SYSTEM
SYS[1] 01
──────────────────────
Settings
──────────────────────
Definition of
parameters for
mixing
In the event of multisystems, you must select the system on
which to modify the parameters.
The 3.4.1.1.1.2 "Settings" section allows accessing and modifying the parameters that affect system operation.
This is why these parameters must not be modified by unqualified personnel.
The Manufacturer cannot be held liable for system malfunctions caused by improper configuration of these
parameters.
A
DDRESS
3 S
ETTINGS
M
ENU
/ 3.4 T
ECHNICAL
M
ENU
/ 3.4.1 P
ASSWORD
M
ENU
/ 3.4.1.1 M
AIN
/ 3.4.1.1.1 S
YSTEM
/
3.4.1.1.1.2 S
ETTINGS
/
3.4.1.1.1.2.1
C
LIMATE
S
CREENSHOT
Table of movements
Button
Screenshot
3.4.1.1.1.2.7 SUPPLY LIMIT TEMPERATURE
3.4.1.1.1.2 SETTINGS
3.4.1.1.1.2.2 WINTER COMPENSATION
SYS[1] Climate 01
──────────────────────
Type:External/Room
Season:Win + Sum:
──────────────────────
Climate and season
Table of variables
No. Description
1
Type of system climate control
2
System seasonal operating mode
Climate with external sensor
Only the external sensor is installed in this type of configuration.
Delivery temperatures calculated according to the external compensation curve. The system activates the boiler/chiller and the
pump, adjusting the mixing valve to the required calculated temperature. Partial disconnection of the system is controlled by
external controls by means of remote thermostats.
Season:
• Winter: Temperature control is activated only during the winter season.
• Summer Temperature control is activated during Summer.
• Summer: Temperature control is activated only during the summer season. Summer configuration requires extra caution on
system external humidity control.
Climate with Ex Room sensor
This type of configuration requires the installation of an external sensor and of at least one HT/H or HT room sensor.
Season:
• Winter: Temperature control is activated only during the winter season. The control unit will deactivate all the summer
functions, dehumidifier control, etc. Compensation occurs considering the external temperature curve and (optional) room
dynamic compensation.
• Summer Temperature control is activated inner Summer. Compensation occurs considering the seasonal
external temperature curve and (optional) room dynamic compensation. During summer, in cooling mode, the logic will
consider the limitation set by the room dew point.
• Summer: Temperature control is activated only during the summer season. The control unit will deactivate all the winter
functions. Compensation occurs considering the external temperature curve and (optional) room dynamic compensation.
The logic will consider the limitation set by the room dew point.