10. Temp Reporting Filter (16-bit)
Set Command Definition
7
6
5
4
3
2
1
0
Command Class = COMMAND_CLASS_CONFIGURATION
Command = CONFIGURATION_SET
Parameter = 0x0A
Default
RESERVED
Size = 0x04
Precision (0x00)
Scale
Bound Size (0x01)
Temperature Filter Lower Bound
Precision (0x00)
Scale
Bound Size (0x01)
Temperature Filter Upper Bound
•
Parameter (8-bit)
The parameter is set to 10 (0x0A) for the temperature
reporting filter.
•
Default (1-bit)
If the default bit is set, the upper bound is zero (0) and the
lower bound is 124. This disables the filter.
•
Size (3-bit)
The Size field must be set to 4 (100b).
•
Precision (3-bits)
The precision field describes the precision of the temperature
filter value. The filter must be zero (0x00).
•
Scale (2-bits)
The scale field indicates the temperature scale used: 0
indicates Celsius and 1 indicates Fahrenheit.
•
Bound Size (3-bits)
The size field indicates the number of bytes used for the
temperature filter value. This field must be one (0x01).
•
Temperature Filter Lower Bound (8-bit)
The thermostat will report ambient temperature changes for
temperature values less than the lower bound. This field must
be between 0F and 124F. By default, this value is 124F (report
all temperature changes).
Summary of Contents for CT102
Page 3: ...3 Radio Thermostat Getting Started ...
Page 11: ...11 Radio Thermostat Setup ...
Page 17: ...17 Radio Thermostat Wiring Diagrams ...
Page 26: ...Radio Thermostat 3 Product Overview ...
Page 34: ...Radio Thermostat 11 Customization ...
Page 48: ...RTCOA logo sheet 7aug07 CT102 THERMOSTAT Z WAVE REFERENCE ...