4
CT102 Thermostat
Z Wave
®
Configuration Parameters
This device supports the following Configuration Parameters:
Name
Set/Get
Default
Values
1
Temp Reporting Threshold
Set/Get
2
0 to 4
2
HVAC Settings
Get Only
N/A
see below
3
Utility Lock Enable/Disable
Set Only
0
0 to 127
4
C- Wire/Battery Status
Get Only
N/A
0 or 1
5
Humidity Reporting Threshold
Set/Get
2
0 to 3
6
Auxiliary/Emergency
Set/Get
0
0 or 1
7
Thermostat Swing Temp
Set/Get
2
1 to 8
8
Thermostat Diff Temp
Set/Get
4
4 to 12
9
Thermostat Recovery Mode
Set/Get
2
1 or 2
10
Temp Reporting Filter
Set/Get
see below
11
Simple UI Mode Enable/Disable
Set/Get
1
0 or 1
12
Multicast Enable/Disable
Set/Get
0
0 or 1
1. Temperature Reporting Threshold (8-bit)
This value determines the reporting threshold when association
reporting is enabled. Unsupported values are ignored.
Value
0
1
2
3
4
Treshhold
Disabled
Disabled
0.5°F
1.0°F
1.5°F
2. HVAC Settings (32-bit)
Byte 1 = HVAC Setup: Normal (0x01) or Heat Pump (0x02)
Byte 2 = Aux Setup (Gas (0x01) or Electric (0x02)) & Number of
Auxiliary Stages (Heat Pump)/Number of Heat Stages
(Normal)
Byte 3 = Number of Heat Pump Stages
Byte 4 = Number of Cool Stages
3. Utility Lock (8-bit)
If set to 0, the utility lock is disabled. All other values (1-255) enable
the utility lock.
Summary of Contents for CT102
Page 3: ...3 Radio Thermostat Getting Started ...
Page 11: ...11 Radio Thermostat Setup ...
Page 17: ...17 Radio Thermostat Wiring Diagrams ...
Page 26: ...Radio Thermostat 3 Product Overview ...
Page 34: ...Radio Thermostat 11 Customization ...
Page 48: ...RTCOA logo sheet 7aug07 CT102 THERMOSTAT Z WAVE REFERENCE ...