As stated above one end of the VTO is for the mounting on the exchanger of the boiler, and
the other is supplied with cold water under pressure. It is particularly important that the water
flow is unobstructed even when the electricity is switched off.
If it is impossible to provide the inflow of cold sanitary water at the time of
electricity switch off , the boiler must be connected onto the open system.
Figure 7. Installation of safety elements
- Thermostats in the automation of the boiler (
Figure 8
)
Within the automation itself that leads the combustion process and influences the work of two
cycles of heating, there are two termostatats. Both are of similar construction as the thermostat
shown in Figure 6 and they have safety functions as limiters of the temperature of water in the
boiler. Because of the safety role in the functioning of the boiler, both thermostats have the
independent probes for measuring of water temperature. The first thermostat is the so-called
„working thermostat” work and it serves to limit the temperature to a level the user wants.
Another thermostat is the „safety thermostat” because it stops the opration of the fan which
favors the flame, and adds a new energy. Safety temperature is limited to 95 degrees Celsius.